![York YCUL0045E Скачать руководство пользователя страница 64](http://html1.mh-extra.com/html/york/ycul0045e/ycul0045e_installation-operation-and-maintenance_4223692064.webp)
JOHNSON CONTROLS
64
FORM 150.63-NM8 (1020)
UNIT CONTROLS
The Display/Print keys allow the user to retrieve system
and unit information that is useful for monitoring chiller
operation, diagnosing potential problems, troubleshoot-
ing, and commissioning the chiller.
System and unit information, unit options, setpoints,
and scheduling can also be printed out with the use of
a printer. Both real-time and history information are
available.
OPER DATA KEY
The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed and
remain on the display until another key is pressed. After
pressing the OPER DATA key, the various operating
data screens can be scrolled through by using the UP
and DOWN arrow keys located under the “ENTRY”
section.
System 2 information will only be dis
-
played for 2 system units.
With the “UNIT TYPE” set as a condensing unit (via
jumper between J11-7 and J11-12 on the I/O Board),
DISPLAY/PRINT KEYS
the following list of operating data screens are view-
able under the Oper Data key in the order that they are
displayed. The
↓
arrow key scrolls through the displays
in the order they appear below:
The chiller MUST be set to be a
condensing unit via jumper between
J11-7 and J11-12 on the I/O Board.
DO NOT operate the equipment if not
properly set up.
This display shows the discharge air temperature leaving
the evaporator. The display will only be shown when the
Control Mode is programmed for Discharge Air (under
the Options key). The minimum limit on the display
for these parameters are 9.2°F (-12.7°C). The maximum
limit on the display is 85.4°F (29.7°C).
This display shows the ambient air temperature. The
minimum limit on the display is 0.4°F (-17.6°C). The
maximum limit on the display is 131.2°F (55.1°C).
A M B I E N T A I R T E M P
= 8 7 . 5 ° F
00067VIP
D I S C H A R G E A I R T E M P
= 5 7 . 4 ° F
Содержание YCUL0045E
Страница 8: ...JOHNSON CONTROLS 8 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 113: ...JOHNSON CONTROLS 113 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 115: ...JOHNSON CONTROLS 115 FORM 150 63 NM8 1020 4...
Страница 119: ...JOHNSON CONTROLS 119 FORM 150 63 NM8 1020 4...
Страница 121: ...JOHNSON CONTROLS 121 FORM 150 63 NM8 1020 4...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 63 NM8 1020 4...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 63 NM8 1020 4...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 63 NM8 1020 4...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 63 NM8 1020 4...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 63 NM8 1020 4...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 63 NM8 1020 4...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 63 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 141: ......
Страница 142: ...NOTES...
Страница 143: ...NOTES...