FIGURE 53 -
INVERTER WIRING
YCAL0033 PROGRAMMING
Condenser fan control type must be programmed un-
der both the OPTIONS and PROGRAM keys when an
VFD is installed on the chiller. Under the OPTIONS
key, FAN CONTROL must be programmed for DIS-
CHARGE PRESSURE CONTROL only. This will as-
sure the condenser fan control is solely by discharge
pressure with no ambient control.
Under the PROGRAM key, the FAN CONTROL ON
PRESSURE should be programmed for 425 PSIG and
the FAN DIFFERENTIAL OFF PRESSURE should be
programmed for 125 PSIG.
TABLE 26 -
YCAL033 VFD LOW AMBIENT OPTION – CONDENSER FAN CONTROL OPERATION
FAN STAGE
ON
OFF
CONTACTOR
MICRO
BOARD
FAN #
SYS 1
SYS 1
SYS 1
1:
VFD CONTROL
(1 FAN
VARIABLE
SPEED)
FAN SPEED
IS A FUNCTION OF
DISCHARGE
PRESSURE.
WHEN THE LIQUID
LINE SOLENOID IS
ENERGIZED. SPEED
INCREASES WITH
PRESSURE
FAN WILL TURN
OFF OR TURN VERY
SLOWLY WHEN
PRESSURE DROPS
BELOW 260 PSIG.
7M
TB7-3
1
2:
1 FAN VFD
CONTROL
2ND FAN
FULL SPEED
UNDER
CONTACTOR
CONTROL
425 PSIG,
BOTH FANS
WILL BE RUNNING
FULL SPEED
DISCHARGE
PRESSURE
< 260 PSIG
(PRESSURE IS
< FAN CONTROL ON
PRESSURE OF
425 PSIG MINUS FAN
DIFFERENTIAL
PRESSURE OF 125
PSIG = 300 PSIG)
7M
&
8M
TB7-3
&
TB7-10
3
Programming as suggested assures the chiller control
points for the second fan in the fan staging sequence
and the inverter control points are matched for opti-
mum control of the fans at reduced ambient tempera-
tures, assuring superheat and oil control is not compro-
mised. When the chiller and VFD fan control points are
programmed properly, the fans will operate as outlined
in Table 26.
Содержание YCAL0019
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Страница 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Страница 127: ...127 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5 DIMENSIONS YCAL0052 SI CONT D...
Страница 129: ...129 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5 DIMENSIONS YCAL0056 SI CONT D...
Страница 191: ...191 JOHNSON CONTROLS SECTION 8 UNIT OPERATION FORM 150 67 NM1 ISSUE DATE 4 28 2017 8 Figure 48 WIRING LD11799A...
Страница 202: ...JOHNSON CONTROLS 202 FORM 150 67 NM1 ISSUE DATE 4 28 2017 SECTION 8 UNIT OPERATION THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...