SECTION 5 - MAINTENANCE
It is the responsibility of the equipment owner to provide
maintenance on the system.
IMPORTANT
If system failure occurs due to improper maintenance
during the warranty period, Johnson Controls will
not be liable for costs incurred to return the system to
satisfactory operation. The following is intended only as
a guide and covers only the chiller unit components. It
does not cover other related system components which
may or may not be furnished by Johnson Controls.
System components should be maintained according to
the individual manufacture’s recommendations as their
operation will affect the operation of the chiller.
COMPRESSORS
Oil Level check
The oil level can only be tested when the compressor is
running in stabilized conditions, to ensure that there is
no liquid refrigerant in the lower shell of the compressor.
When the compressor is running at stabilized conditions,
the oil level must be between 1/4 and 3/4 in the oil sight
glass. Note: at shutdown, the oil level can fall to the
bottom limit of the oil sight glass. Use YORK “F” oil
when adding oil.
Oil Analysis
The oil used in these compressors is pale yellow in color
(mineral oil). If the oil color darkens or exhibits a change
in color, this may be an indication of contaminants in the
refrigerant system. If this occurs, an oil sample should
be taken and analyzed. If contaminants are present, the
system must be cleaned to prevent compressor failure.
Never use the scroll compressor to pump
the refrigerant system down into a vac
-
uum. Doing so will cause internal arcing
of the compressor motor which will re
-
sult in failure of compressor.
CONDENSER FAN MOTORS
Condenser fan motors are permanently lubricated and
require no maintenance.
CONDENSER COILS
Dirt should not be allowed to accumulate on the
condenser coil surfaces. Cleaning should be as often as
necessary to keep coil clean.
Exercise care when cleaning the coil so
that the coil fins are not damaged.
OPERATING PARAMETERS
Regular checks of the system should be preformed to
ensure that operating temperatures and pressures are
within limitations, and that the operating controls are
set within proper limits.
Refer to the Operation, Startup,
and Installation sections of this manual.
ON-BOARD BATTERY BACK-UP
U5 (031-02565-000) on the IPU2 Board is the Real
Time Clock chip that maintains the date/time and stores
customer programmed setpoints.
The unit evaporator heater is 120VAC.
Disconnecting 120VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.
OVERALL UNIT INSPECTION
In addition to the checks listed on this page, periodic
overall inspections of the unit should be accomplished
to ensure proper equipment operation. Items such as
loose hardware, component operation, refrigerant leaks,
unusual noises, etc. should be investigated and corrected
immediately.
Содержание YCAL0014E Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ...JOHNSON CONTROLS 10 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 18: ...JOHNSON CONTROLS 18 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 31: ...JOHNSON CONTROLS 31 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 126: ...JOHNSON CONTROLS 126 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 140: ...JOHNSON CONTROLS 140 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM8 1020 5 6 ...
Страница 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM8 1020 5 6 LD08855 ...
Страница 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM8 1020 161 5 6 ...
Страница 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM8 1020 5 6 ...
Страница 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM8 1020 5 6 ...
Страница 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM8 1020 5 6 ...
Страница 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM8 1020 5 6 ...
Страница 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM8 1020 5 6 ...
Страница 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM8 1020 5 6 ...
Страница 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM8 1020 5 6 ...
Страница 181: ...JOHNSON CONTROLS 181 FORM 150 62 NM8 1020 5 6 ...
Страница 183: ...JOHNSON CONTROLS 183 FORM 150 62 NM8 1020 5 6 LD08833 ...
Страница 185: ...JOHNSON CONTROLS 185 FORM 150 62 NM8 1020 5 6 ...
Страница 187: ...JOHNSON CONTROLS 187 FORM 150 62 NM8 1020 5 6 ...
Страница 189: ...JOHNSON CONTROLS 189 FORM 150 62 NM8 1020 5 6 ...
Страница 191: ...JOHNSON CONTROLS 191 FORM 150 62 NM8 1020 5 6 ...
Страница 195: ...JOHNSON CONTROLS 195 FORM 150 62 NM8 1020 5 6 ...
Страница 197: ...JOHNSON CONTROLS 197 FORM 150 62 NM8 1020 5 6 ...
Страница 199: ...JOHNSON CONTROLS 199 FORM 150 62 NM8 1020 5 6 ...
Страница 200: ...JOHNSON CONTROLS 200 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 211: ...JOHNSON CONTROLS 211 FORM 150 62 NM8 1020 THIS PAGE INTENTIONALLY LEFT BLANK ...