background image

FORM 160.00-NO7

YORK INTERNATIONAL

YORK INTERNATIONAL

YORK INTERNATIONAL

4

3

2

FORM 160.00-NO7

SPECIFICATIONS

Part Number

WAEXRK01

Applicable

Variable Speed Oil Pump Drive on Mod D (and later) YK chillers

Controls

with software revision 12.1 or higher

Communication

4-conductor telephone modular type (RJll)

Cable

(6 position, 4 contact standard extension cable)

Max Communication Distance

300 feet

Keypad

8 keys for operation and programming

Display

6-digit, backlit LCD with special annunciators and unit symbols

LED Indicator

Red or green STATUS indicator

Enclosure

NEMA 1 molded plastic case

Power Source

9-volt alkaline battery or AC adapter

Low Battery

Low battery indicator and staged power-down

FIG. 1 – 

REMOTE KEYPAD UNIT (RKU)

INSTALLING THE BATTERY

To install the 9-volt alkaline battery in the RKU, remove

the battery access cover on the back of the unit and

snap the connector onto the battery terminals as shown

in Figure 2. Replace the battery access cover. Also see

Low Battery Power section at the end of this manual.

CONNECTING TO THE VSOP DRIVE

The Remote Keypad Unit is supplied with an intercon-

nection cable that allows it to communicate with an VSOP

Drive. One end of the cable connects to connector J22

on the VSOP Drive and the other connects to Jl on the

RKU. These connections are fully isolated, however

CARE  SHOULD  BE  TAKEN  WHEN  CONNECT-

ING  CABLE  AS  LETHAL  VOLTAGES  CAN  BE

PRESENT. Refer to Figure 3.

The Remote Keypad Unit can be connected and dis-

connected  to  the  VSOP  Drive  at  any  time,  however

compatibility varies with different VSOP Drive soft-

ware revisions (displayed in parameter 02-RVLVL of

every  VSOP  Drive).  Table  1  below  summarizes  the

RKU operation with the various software versions of

VSOP Drive. Refer to the VSOP Drive Operation and

Maintenance manual, for more information.

Hazard  of  electrical  shock.  Discon-

nect power to the VSOP Drive before

working  on  this  drive.  Dangerous

voltages exist in the VSOP Drive un-

til the STATUS Indicator is off.

TABLE 1 – 

RKU OPERATION

VSOP 02-RVLVL

REMOTE KEYPAD OPERATION WITH RKU

11.8

Not compatible with these drives

12.1

1.  Normal  operation.
2. STATUS indicator on RKU remains on at all times.

12.3

1.  Normal  operation.
2. STATUS indicator on RKU remains on at all times.

13.1

1.  Normal  operation.
2. STATUS indicator operates normally.

OPERATION

POWER ON AND OFF

Battery Power

 

– 

To turn the RKU on, press and re-

lease the 

PROGram 

key. To turn the RKU off press

and release the 

SHIFT 

key twice within one second.

INDICATIONS

When the Remote Keypad Unit is first turned on, all

segments in the LCD display will illuminate for about 2

seconds and the STATUS indicator will flash red. If the

RKU is not connected to an VSOP Drive the display

shown in Figure 5 will appear indicating that the option

is not communicating with the drive. This indication will

also indicate if the RKU is properly connected but the

drive does not have power applied to it.

FIG. 5 – 

NO COMMUNICATION

15+

F

When  the  Remote  Keypad  Unit  is  connected  to  an

VSOP Drive that has AC power applied, the display

will show the current operating status of the drive. That

is, if the VSOP drive is in the operating mode it will

display the current operating frequency and direction.

For  any  other  fault  codes,  contact  the  factory  for  assistance.

FAULT

CAUSE

REMEDY

CODE

01

Computer  Malfunction

Reset the drive by pressing the stop button for longer than 1 second.

05

No DC Bus Voltage

Check for proper source voltage.

06

Output Short Circuit

Check  motor  wiring.

11

Ground Fault

Check  motor  wiring.

13

Overvoltage on the DC Bus

1. Verify line voltage.
2. Check for power factor correction capacitors on the incoming power.

18

Running  Overcurrent

Locate cause of oil pump loading.

19

Heatsink  Over  Temperature

1. Check for excessive overload.
2. Locate the VSOP drive in a cooler location.

20

Timed Overload

Check for overload on the oil pump motor.

21

DC  Undervoltage

Verify line voltage.

LD04348

FIG. 2 – 

INSTALLING BATTERY

LD04349

FIG. 6 – 

OPERATING MODE

00104VIP

TYPICAL USAGE

Typical usage of the Remote Keypad Unit is to view

fault data. The following steps should be followed to

view fault data.

1. Install the Remote Keypad Unit as directed in the

previous section.

2. Press the PROG/ON button. The frequency of the

drive’s output should be displayed.

3. Press  and  hold  the  SHIFT  button  then  press  the

PROG button. The parameter number shall appear

in the upper left hand corner of the display.

4. Use the UP & DOWN arrow buttons to select pa-

rameter number 7, 8,and 9.

5. Press the SHIFT button twice to turn the RKU off.

Parameter number 7 is the location for the fault code of

the last fault. Parameter number 8 is the location for the

fault code of the second fault. Parameter number 9 is

the location for the fault code of the first fault.

FIG. 3 – 

INTERCONNECTION CABLE

J22

VARIABLE

SPEED OIL

PUMP DRIVE

INTERCONNECTING

CABLE

J1

REMOTE

KEYPAD

UNIT

00102VIP

Содержание WAEXRK01

Страница 1: ...an be accessed while the RKU is connected or disconnected from an VSOP Drive To program parameter AP Auto Power Down or bL Backlight Control use the following program mingmethod 1 Press the UP DOWN arrow keys to access the de sired parameter The parameter number will be dis played in the upper left corner of the digital display 2 Press the SHIFT key to allow the data code to be changed The PRG ind...

Страница 2: ...F Battery Power To turn the RKU on press and re lease the PROGram key To turn the RKU off press and release the SHIFT key twice within one second INDICATIONS When the Remote Keypad Unit is first turned on all segments in the LCD display will illuminate for about 2 seconds and the STATUS indicator will flash red If the RKU is not connected to an VSOP Drive the display shown in Figure 5 will appear ...

Страница 3: ...F Battery Power To turn the RKU on press and re lease the PROGram key To turn the RKU off press and release the SHIFT key twice within one second INDICATIONS When the Remote Keypad Unit is first turned on all segments in the LCD display will illuminate for about 2 seconds and the STATUS indicator will flash red If the RKU is not connected to an VSOP Drive the display shown in Figure 5 will appear ...

Страница 4: ...F Battery Power To turn the RKU on press and re lease the PROGram key To turn the RKU off press and release the SHIFT key twice within one second INDICATIONS When the Remote Keypad Unit is first turned on all segments in the LCD display will illuminate for about 2 seconds and the STATUS indicator will flash red If the RKU is not connected to an VSOP Drive the display shown in Figure 5 will appear ...

Страница 5: ...an be accessed while the RKU is connected or disconnected from an VSOP Drive To program parameter AP Auto Power Down or bL Backlight Control use the following program mingmethod 1 Press the UP DOWN arrow keys to access the de sired parameter The parameter number will be dis played in the upper left corner of the digital display 2 Press the SHIFT key to allow the data code to be changed The PRG ind...

Страница 6: ...an be accessed while the RKU is connected or disconnected from an VSOP Drive To program parameter AP Auto Power Down or bL Backlight Control use the following program mingmethod 1 Press the UP DOWN arrow keys to access the de sired parameter The parameter number will be dis played in the upper left corner of the digital display 2 Press the SHIFT key to allow the data code to be changed The PRG ind...

Отзывы: