SECTION 4 - CYCLING SHUTDOWNS
MESSAGE
DESCRIPTION
VSD - High Phase A (or B, C)
Instantaneous Current
PHASE A (OR B, C)
OVERCURRENT FAULT
This shutdown is generated by the OSCD logic board. If any one phase of motor
current as measured by the Output Current Transformers exceeds a threshold.
Refer to the chart below for the shutdown threshold value.
DRIVE HP RATING
THRESHOLD SHUTDOWN VALUE
270, 292, 351, 424
771 Amps Peak
385, 419, 503, 608
1200 Amps Peak
546, 575, 608 (400VAC),
658, 704, 750 790,
1890 Amps Peak
900, 914, 917, 948, 1055, 1100
2749 Amps Peak
If an Instantaneous Current Fault occurs but the chiller restarts and runs without a
problem, the cause may be attributed to a voltage sag on the utility power feeding
the OSCD that is in excess of the specified dip voltage rating for this product. This
is especially true if the chiller was running at, or near, full load. If there is a sudden
dip in line voltage, the current to the motor will increase. The chiller vanes cannot
close quickly enough to correct for this sudden increase in current and the chiller
will trip on this fault.
VSD - Initialization Failed
VSD INITIALIZATION FAILED
At power-up, the OSCD logic board will go through a process called initialization. At
this time, memory locations are cleared, jumper positions are checked, and com
-
munications links are established between the OSCD logic board, and the Control
Center.
VSD - Invalid Current Scale
Selection
INVALID CURRENT SCALE FAULT
The J1 connector on the OSCD logic board contains jumpers along with wires from
the output CTs. The jumpers configure the OSCD logic board to the HP rating of
the OSCD being used in this application in order to properly scale the output cur-
rent. If the jumper configuration is found by the logic board to be invalid, the system
will be shut down and the above message will be generated. The proper jumper
configuration is shown on the wiring label for the OSCD.
VSD - Logic Board Power
Supply
MAIN BOARD POWER
SUPPLY
This shutdown is generated by the OSCD logic board, and it indicates that one of
the low voltage power supplies for the OSCD logic board has dropped below their
allowable operating limits. The power supplies for the logic boards are derived from
the secondary of the 120 to 24 VAC transformer which in turn is derived from the
480 to 120 VAC control transformer.
VSD - Logic Board Processor
PWM COMMUNICATIONS FAULT
This shutdown is generated by the OSCD logic board. If a communications
problem occurs between the two microprocessors on the OSCD logic board this
shutdown will occur.
VSD - Low Converter
Heatsink Temperature
LOW CONV HEATSINK TEMP.
A thermistor sensor is located on the SCR/Diode block side of the copper chill plate
on the OSCD Power Unit. Anytime this thermistor detects a temperature of 37°F
(3°C) or lower a shutdown will occur.
VSD - Low DC Bus Voltage
LOW DC BUS VOLTAGE FLT
If the line voltage were to quickly drop the current seen by the motor could exceed
it’s rating. The low bus voltage shutdown will prevent this from happening. The
shutdown is generated when the DC link voltage drops below 500 VDC for 460
VAC input voltage, 414 VDC for 380, 400, and 415 VAC input voltage or 600 VDC
for 575 VAC input voltage.
TABLE 4 -
CYCLING SHUTDOWN MESSAGE (CONT'D)
Содержание VSD 292
Страница 30: ...JOHNSON CONTROLS 30 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 34: ...JOHNSON CONTROLS 34 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 40: ...JOHNSON CONTROLS 40 FORM 160 00 O4 ISSUE DATE 07 31 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 42: ...THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS 42 FORM 160 00 O4 ISSUE DATE 07 31 2019...