Johnson Controls Ducted Systems
PERFORMANCE DATA - 3 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
120 °F
T (°F)
P (PSIG)
MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW
TCHE36S41S1
35
107
33.3
3.24
31.8
3.24
30.2
3.24
28.6
3.24
26.9
3.24
25.0
3.24
23.0
3.24
21.9
3.24
40
118
36.6
3.22
35.0
3.22
33.3
3.22
31.6
3.22
29.7
3.22
27.7
3.22
25.5
3.22
24.4
3.22
45
130
40.1
3.20
38.4
3.20
36.7
3.20
34.8
3.20
32.8
3.20
30.6
3.20
28.3
3.20
27.0
3.20
50
142
43.9
3.18
42.1
3.18
40.2
3.18
38.2
3.18
36.0
3.18
33.7
3.18
31.2
3.18
29.8
3.18
55
156
47.8
3.09
45.9
3.16
43.9
3.16
41.8
3.16
39.4
3.16
36.9
3.16
34.3
3.16
32.9
3.16
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCHE36S41S1
INDOOR COIL MODEL NO.
FC38C
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
55 / 45
T.C.
34.1
37.0
36.9
39.8
42.1
35.6
38.0
37.9
40.9
42.9
37.1
39.0
38.9
41.9
43.6
S.C.
32.9
31.6
27.0
26.5
21.1
34.3
34.3
29.0
28.3
22.0
35.7
37.0
31.1
30.1
22.8
K.W.
1.89
1.91
1.88
1.90
1.92
1.96
1.98
1.96
1.98
2.00
2.04
2.06
2.05
2.06
2.09
65 / 55
T.C.
33.2
35.7
35.7
38.7
41.4
34.7
36.8
36.7
39.7
42.2
36.2
37.9
37.7
40.7
43.0
S.C.
32.0
30.9
26.6
26.3
21.0
33.4
33.6
28.8
28.3
22.1
34.9
36.2
31.0
30.4
23.2
K.W.
2.07
2.09
2.07
2.08
2.08
2.15
2.16
2.14
2.15
2.16
2.22
2.23
2.22
2.23
2.25
75 / 63
T.C.
32.3
34.5
34.6
37.6
40.7
33.8
35.6
35.6
38.6
41.6
35.3
36.8
36.5
39.6
42.4
S.C.
31.1
30.3
26.2
26.1
21.0
32.5
32.9
28.5
28.4
22.3
34.0
35.4
30.9
30.6
23.5
K.W.
2.25
2.28
2.26
2.26
2.24
2.33
2.35
2.32
2.33
2.32
2.40
2.41
2.39
2.40
2.40
85 / 69
T.C.
31.4
33.4
33.2
36.3
39.3
32.8
34.5
34.1
37.2
40.1
34.3
35.7
35.0
38.1
40.9
S.C.
30.2
29.9
25.5
25.5
20.5
31.6
32.1
27.9
27.9
21.9
33.0
34.4
30.3
30.2
23.3
K.W.
2.49
2.54
2.52
2.51
2.49
2.56
2.60
2.58
2.58
2.57
2.63
2.67
2.64
2.65
2.64
95 / 75
T.C.
30.5
32.4
31.8
35.0
38.0
31.9
33.5
32.6
35.8
38.7
33.3
34.5
33.4
36.6
39.5
S.C.
29.4
29.6
24.9
25.0
20.0
30.7
31.4
27.3
27.4
21.5
32.0
33.3
29.7
29.8
23.0
K.W.
2.73
2.79
2.77
2.76
2.74
2.80
2.85
2.84
2.83
2.81
2.87
2.92
2.90
2.90
2.88
105 / 83
T.C.
29.2
30.8
30.1
33.2
36.2
30.6
32.0
30.9
34.0
36.9
31.9
33.2
31.7
34.8
37.6
S.C.
28.2
28.6
24.2
24.3
19.4
29.4
30.3
26.5
26.7
20.9
30.7
32.0
28.9
29.1
22.4
K.W.
3.16
3.20
3.20
3.14
3.08
3.19
3.23
3.25
3.19
3.15
3.22
3.26
3.29
3.24
3.22
115 / 89
T.C.
28.0
29.3
28.5
31.5
34.5
29.3
30.6
29.2
32.3
35.1
30.6
31.9
30.0
33.0
35.8
S.C.
26.9
27.7
23.4
23.7
18.7
28.2
29.2
25.7
26.0
20.3
29.5
30.7
28.1
28.4
21.8
K.W.
3.58
3.59
3.62
3.50
3.41
3.57
3.59
3.65
3.54
3.48
3.56
3.59
3.67
3.58
3.55
120 / 95
T.C.
26.7
27.9
26.9
29.8
32.7
28.0
29.2
27.6
30.5
33.3
29.3
30.6
28.3
31.2
34.0
S.C.
25.7
26.8
22.7
23.0
18.1
27.0
28.1
25.0
25.4
19.7
28.2
29.4
27.2
27.7
21.2
K.W.
3.99
3.99
4.04
3.86
3.75
3.94
3.96
4.04
3.89
3.81
3.90
3.92
4.05
3.92
3.87
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.