Operation
User Action or Recommended Setting
Description
BACnet IP – Dynamic
IP Address
BACnet IP – Static IP
Address
Default/Range
IP Mask
Read-only status of the IP mask in
use
Read-only status of the
IP mask in use
Read-only status of the
IP mask in use
0.0.0.0 to
255.255.255.255
IP Router
Address
Read-only status of the IP router
address in-use
Read-only status of the
IP router address in use
Read-only status of the
IP router address in use
0.0.0.0 to
255.255.255.255
Table 29: BACnet MS/TP Settings
User Action or Recommended Setting
Description
Wired Field
Bus
Wireless
Field Bus
N2 Field
Bus
Modbus
Field Bus
Default/
Range
Address
The MS/TP MAC address of the unit
you select must not conflict with any
other MS/TP device on the same wire.
For other field devices connected to
the same RS-485 bus, use sequential
addressing. No single MAC address
can be used by more than one device
Set to
the MAC
address
reserved for
the unit
Set to
the MAC
address
reserved for
the unit
Set to
the MAC
address
reserved for
the unit
Set to
the MAC
address
reserved for
the unit
4 / 4–255
Baud
Rate
The RS-485 BACnet connection
requires a specified baud rate in order
to initiate communication with field
devices that may use auto-baud rate
configuration
Set to the
baud rate of
the trunk
(not used)
(not used)
(not used)
38400 bps
Device
OID
The device ID is the instance number
for the BACnet device. This number
must be unique across the building
networks for all device instances
Set to the
device OID
reserved for
the unit
Set to the
device OID
reserved for
the unit
(not used)
(not used)
0–4194302
Table 28: BACnet IP Settings (Continued)
Mobile Access Portal (MAP) Gateway
The mobile access portal (MAP) gateway provides a
wireless mobile user interface to the Smart Equipment.
The MAP gateway gives access to any Smart Equip-
ment device that is on a connected BACnet (MS/TP)
field bus. The intuitive, browser-based interface dis-
plays the same menus as the local user interface.
NOTE:
The Applied Smart Equipment controller is only
compatible with MAP 5.0 and above.
For related documentation, including how to set up param-
eters, and training videos, visit uLearn at
kzoplatform.com/containers/957891534378768109?
.
Table 30: MAP Gateway Related Documentation
Topic
Document
Getting up and running
quickly with the MAP
gateway
Mobile Access Portal Gateway
Quick Start Guide
(Part No. 24-10737-16)
Installing and wiring a
MAP gateway
Mobile Access Portal Gateway
Installation Instructions
(Part No. 24-10737-8)
LD28042
Figure 43: MAP Gateway Dashboard