7.4 Operation Modes and Functions
7.4.1 Fan mode
(
1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled,
and no setting temperature is displayed.
(3) Indoor fan can be set to
high/med/low/auto.
(4) The louver operates same as in cooling
mode.
(5) Auto fan:
a
b
c
d
T1
e
7.4.2 Cooling Mode
7.4.2.1 Compressor running rules
When T1-Ts<
ΔT -2
℃
, the compressor will stop,
when T1
—
Ts >
ΔT -0.5
℃,
the compressor will
be activated.
ΔT is the programmed parameter of
temperature compensation.
When the AC run in mute mode, the
compressor will run with low frequency.
When the current is more than setting value,
the current protection function will be activated,
and the compressor will stop.
7.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan
speed according to T4.
For different outdoor units, the fan speeds are
different.
T4
A+
A
B
C
D
E
7.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time
and the speed can be selected as high,
medium, low and auto.
The indoor fan is controlled as below:
Setting fan
speed
Actual fan speed
H+(H+=H+G)
A
H(=H)
B
C
M+(M+=M+Z)
D
M(M=M)
E
F
L+(L+=L+D)
G
L(L=L)
H
I
T1-Td
℃
(°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
The auto fan acts as below rules:
a
b
c
d
T1
e
7.4.2.4 Condenser temperature protection
T3
Resume
Off
Decrease
Hold
Increase
Содержание Pyrenees Series
Страница 8: ...6 For YHKE09XJ6AMC RX YHKE12XJ6AMC RX For YHKE18XJ6AMC RX YHKE24XJ6AMC RX...
Страница 9: ...7 For YHKE30XJ6AMC RX YHKE36XJ6AMC RX...
Страница 13: ...11 For YHKE18YJ6AMAO X...
Страница 22: ...20 port Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 53: ...M Pyrenees 160101...