JOHNSON CONTROLS
38
FORM 160.79-O3
ISSUE DATE: 11/09/2018
SECTION 2 – OPTIVIEW CONTROL CENTER
This screen displays a cutaway view of the chiller
condenser. Animation indicates condenser liquid flow.
This screen also serves as a gateway to controlling the
Refrigerant Level.
DISPLAY ONLY
Entering Condenser Liquid Temperature
Displays the water temperature as it enters the
condenser.
Leaving Condenser Liquid Temperature
Displays the water temperature as it leaves the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Condenser Small Temperature Difference
Displays the difference between the Condenser Refrig-
erant temperature and the Leaving Condenser Liquid
temperature. The Condenser Refrigerant temperature
will be represented by the Condenser Saturation tem-
perature.
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Drop Leg Refrigerant Temperature
Displays the temperature of the refrigerant in the drop
leg between the condenser and evaporator shells, if the
sensor is present and "Enabled".
Sub-Cooling Temperature
Displays the difference between the Condenser Refrig-
erant temperature and the Drop Leg Refrigerant tem-
perature. The Condenser Refrigerant temperature will
be represented by the Condenser Saturation tempera-
ture. If the Drop Leg sensor is not present, this tem-
perature is not displayed.
Condenser Liquid Flow Switch (Open /
Closed)
Indicates whether flow is present in the condenser.
Condenser Liquid Pump (Run / Stop)
Indicates whether Condenser liquid pump is operating.
Condenser Refrigerant Level
Displays the present position of the refrigerant level.
Active Level Setpoint
Displays the setpoint to which the refrigerant level is
being controlled.
CONDENSER SCREEN
LD27846
FIGURE 7 -
CONDENSER SCREEN