Technical Guide

SPLIT-SYSTEM

EVAPORATOR BLOWERS

NE090, NE/NF120, NE180 & NE240

7.5 THRU 20 NOMINAL TONS

(Export Only  R-410A)

679948-YTG-A-0111

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

The 7.5 thru 10 Ton Evaporator Blowers are single piece units which
include a well-insulated cabinet, a DX cooling coil with copper tubes
and aluminum fins, expansion valve(s), distributor(s), throwaway fil-
ters, a centrifugal blower, a blower motor, an adjustable belt drive and
a blower motor contactor.

These units are shipped in the vertical position ready for field installa-
tion. They can be installed for horizontal operation by reversing the
position of the solid bottom panel with the return air duct flange on the
front of the unit.

The 15 and 20 ton evaporator blowers are designed with two distinct
modules to provide maximum application flexibility. The units are
shipped as single packages with the blower module mounted on top of
the coil module. The blower module can be repositioned in the field to
meet almost any installation requirement.

The 15 Ton blower module includes the blower wheel, motor and
drive. The 20 Ton blower module includes the blower wheels and room
for a field mounted motor and drive. 

The coil modules include direct expansion coils, one inch throwaway
filters, liquid line solenoid valve for 50% capacity reduction, thermal
expansion valves, distributors and a condensate drain pan. Each coil
module also includes a solenoid valve for non-recycling pumpout.
When the cooling requirement in the condition space is satisfied, the
refrigerant is pumped into the high side of the system.

ACCESSORIES—FIELD INSTALLED

SUPPLY AIR PLENUMS

These fully insulated plenums are available for free standing units
located within the conditioned space, are shipped knocked-down for
easy field assembly, are finished to match the exterior of the basic
unit, and have double deflection grills that can be adjusted to vary the
throw, spread and drop of the supply air.

RETURN AIR GRILLS

These expanded metal grills are available for free standing units
located within the conditioned space, are finished to match the exterior
of the basic unit and are shipped in one piece for easy installation.

BASES

Bases are available to raise vertical units above the floor. Outdoor air
may be introduced through these bases by cutting an access opening
to accommodate the outdoor air duct connection. These bases are fin-
ished to match the exterior of the basic unit. They may require field fur-
nished insulation for certain applications.

THREE-PHASE ELECTRIC HEATERS (7.5 THRU 15 TON 
ONLY)

Electric heaters are available in several capacities to provide maxi-
mum flexibility. Both the air conditioning unit and the heater can be
selected to precisely match the cooling and heating requirements of
the conditioned space. These heaters are designed for easy field
installation over the supply air opening of the unit. They have been
tested by and will be shipped with a CSA label. Every heater will be
fully protected against excessive current and temperature by fuses
and two high limit thermostats.

Units with electric heat will require only one power supply for both the
heating elements and the supply air blower motor, and the power wir-
ing can be protected by either dual element/time delay fuses or an
inverse time circuit breaker.

Содержание NE090

Страница 1: ...refrigerant is pumped into the high side of the system ACCESSORIES FIELD INSTALLED SUPPLY AIR PLENUMS These fully insulated plenums are available for free standing units located within the conditioned...

Страница 2: ...20 NE180 7 6 HEATING CAPACITY ELECTRIC HEAT ACCESSORY NE090 NE NF120 NE180 8 7 STEAM COIL CAPACITY MBH 2 PSIG 9 8 HOT WATER CAPACITY MBH 9 9 PRESSURE DROP VS GPM 9 10 CAPACITY CORRECTION VS GPM 9 11 S...

Страница 3: ...he top of the unit Hanger rods must be field furnished THERMOSTATS Wall mounted thermostats and subbases 24 volt with sys tem and fan switches are available to control the operation of these split sys...

Страница 4: ...d in the exterior panels for access to these weld nuts Hanger rods must be field supplied MODEL 15 TON The unit has two distinct modules a blower module and a coil module The unit is shipped in the ve...

Страница 5: ...xibility The Supply Air Plenum Return Air Grill and Base acces sories can be applied on arrangements 1 4 The Return Air Grill and Base accessories can be applied on arrangements 2 3 4 6 The Supply Air...

Страница 6: ...END OF THE UNIT 4 3 8 16 WELD NUTS RETURN AIR GRILL HOT WATER COIL AND STEAM COIL ACCESSORIES INSTALLED ONTHIS END OF THE UNIT B C A D Y X TABLE 1 UNIT SUSPENSION MOUNTING HORIZONTAL APPLICATION WEIG...

Страница 7: ...L SUSPENSION CHANNEL 43 3 4 5 A B C D E F 55 HANGER RODS FIELD SUPPLIED TABLE 3 OPERATING WEIGHTS LB NE090 NE NF120 NE180 MODEL 090 120 180 BASIC UNIT Cooling Only 320 355 425 ACCESSO RIES Base 55 55...

Страница 8: ...4803 2HS045036 25 208 2402 36 123 16 54 7 20 68 3 46 4803 180 2HS045010 25 208 2402 10 34 2 10 34 2 46 2803 2HS045016 25 208 2402 16 54 7 10 34 2 6 20 5 46 2803 2HS045026 25 208 2402 26 88 9 16 54 7 1...

Страница 9: ...cities do not include any blower motor heat 2 Multiply these capacities by the following factors to correct for higher steam pressures Steam Pressure psig 5 10 15 20 25 Capacity correction factor 1 06...

Страница 10: ...880 1667 1 79 944 1798 1 93 4400 792 1510 1 62 843 1629 1 75 901 1759 1 89 965 1890 2 03 4600 813 1599 1 72 864 1718 1 84 922 1848 1 98 986 1979 2 12 CFM EXTERNAL STATIC PRESSURE 1 0 1 2 1 4 1 6 RPM...

Страница 11: ...5200 861 2352 2 52 920 2562 2 75 972 2718 2 92 1022 2847 3 05 5400 884 2538 2 72 943 2748 2 95 995 2905 3 12 1045 3033 3 25 5600 907 2728 2 93 966 2939 3 15 1019 3095 3 32 1069 3224 3 46 CFM EXTERNAL...

Страница 12: ...9 3 54 6800 690 2753 2 95 729 2991 3 21 768 3222 3 46 811 3456 3 71 7000 701 2915 3 13 740 3153 3 38 780 3384 3 63 823 3618 3 88 CFM EXTERNAL STATIC PRESSURE 1 0 1 2 1 4 1 6 RPM W BHP RPM W BHP RPM W...

Страница 13: ...14 0 18 3200 0 02 0 04 0 06 0 09 0 05 0 05 0 16 0 20 3400 0 02 0 04 0 07 0 10 0 05 0 05 0 17 0 23 3600 0 02 0 05 0 07 0 11 0 06 0 06 0 19 0 25 3800 0 02 0 06 0 08 0 12 0 06 0 06 0 22 0 27 4000 0 03 0...

Страница 14: ...25 37 21 10 45 70 29 43 19 9 34 53 54 82 10 5 3600 920 71 110 28 41 22 11 50 79 32 47 20 10 38 60 60 91 11 6 4000 1025 78 123 30 45 22 11 56 88 35 52 20 10 42 66 67 102 11 6 4400 1130 86 135 33 49 23...

Страница 15: ...3 2 TABLE 22 PHYSICAL DATA NE NF Component Description Model 90 120 180 240 EVAPORATOR BLOWER1 Centrifugal Blower Dia X Wd in 15 X 15 15 X 15 18 X 18 2 X15 X 12 Fan Motor HP Belt Drive 1 1 2 2 3 3 5 E...

Страница 16: ...7 8 15 AIR OUT BLOWER MOTOR AND DRIVE ACCESS PANEL This side only 51 1 8 HOLE WITH GROM MET FOR 1 2 O D LIQUID LINE HOLE WITH GROM MET FOR 1 1 8 O D SUCTION LINE 4 2 5 8 1 3 8 1 3 4 1 1 8 25 1 8 2 7...

Страница 17: ...L Filters can be removed through either side of the unit 1 1 4 KNOCKOUT FOR LIQUID CONNECTION COIL SECT BLOWER SECTION Refer to INSTALLING REFRIGERANT MAINS in installation instruction when piping thr...

Страница 18: ...SIDE PANEL 20 3 8 26 3 4 29 1 2 A B EVAPORATOR COIL SECTION 2 5 16 C AIR IN AIR IN All dimensions are in inches They are subject to change without notice Certi fied dimensions will be provided upon r...

Страница 19: ...52 180 60 3 4 31 27 55 3 4 19 7 8 6 1 8 1 2 1 2 19 1 2 1 1 2 1SP0405 240 89 1 2 30 3 4 24 5 8 37 1 2 6 5 8 3 15 16 17 1 4 3 5 8 1 1 2 5 1 2 24 3 18 E G F H D A H B L K C 1SP0451 SHIPPED KNOCKED DOWN F...

Страница 20: ...ory to the basic unit It is provided with a squeeze connector for securing the wiring harness and its location corresponds to the loca tion of the 1 23 32 knockout in the top panel of the basic unit C...

Страница 21: ...wer section of the unit 180 60 3 4 32 1 4 6 3 5 16 3 3 8 17 3 8 1 1 2 1NF04532 240 89 1 2 30 3 4 6 3 7 16 3 15 16 14 15 16 1 1 2 FIGURE 16 HOT WATER COIL C A B D E F G 2 CONN S 2 H Coil Model Unit Mod...

Страница 22: ...6 None 8 3 15 10 KW 7 5 1 20 8 34 3 35 16 KW 12 2 33 4 49 9 50 26 KW 19 5 2 54 2 76 0 80 36 KW 27 2 75 1 102 1 110 230 3 60 6 8 None 8 5 15 10 KW 10 1 24 1 38 6 40 16 KW 16 2 38 5 56 6 60 26 KW 26 2...

Страница 23: ...208 3 60 14 0 None 17 5 20 230 3 60 14 0 None 17 5 20 460 3 60 7 0 None 8 8 15 1 Minimum Circuit Ampacity 2 Dual Element Time Delay Type 3 HACR type per NEC TABLE 33 ELECTRICAL DATA EVAPORATOR UNITS...

Страница 24: ...ubject to change without notice Printed in U S A 679948 YTG A 0111 Copyright by Unitary Products Group 2011 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 7306...

Отзывы: