351579-YTS-B-0608
42
Johnson Controls Unitary Products
Table 13: Alarm Default Codes
Code
Cause
1
Compressor number one locked out on High Pressure Control
2
Compressor number two locked out on High Pressure Control
3
Compressor number three locked out on High Pressure Control
4
Compressor number four locked out on High Pressure Control
5
Compressor number one locked out on Low Pressure Control
6
Compressor number two locked out on Low Pressure Control
7
Compressor number three locked out on Low Pressure Control
8
Compressor number four locked out on Low Pressure Control
13
First stage heating is locked out due to excessive Limit Switch Trips
14
Second stage heating is locked out due to excessive Limit Switch Trips
15
Third stage heating is locked out due to excessive Limit Switch Trips
16
First stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas
valve has voltage on it and the control is not calling for this stage of heating
17
Second stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the
gas valve has voltage on it and the control is not calling for this stage of heating
18
Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas
valve has voltage on it and the control is not calling for this stage of heating
19
Space Temperature Sensor has failed open or shorted
20
Supply Air Temperature Sensor has failed open or shorted
21
Return Air Temperature Sensor has failed open or shorted
22
Outside Air Temperature Sensor has failed open or shorted
23
Dirty Filter Switch has tripped
24
Unit has locked out on the APS. Air Pressure Switch.
25
The APS is stuck closed.
26
A microelectronics failure has occurred and the control is operating on defaults
27
A microelectronics failure has occurred and the control is down due to a fatal fault.
28
The control is locked out due to Fan Overload Trips
29
Outside Humidity Sensor is out of Range
30
Return Air Humidity Sensor is out of Range
31
IAQ Sensor is out of Range
32
Real Time Clock cannot be read and has a hardware failure
33
Space Temperature Offset is greater than 20K Ohms
34
CV/VAV input is out of range and the unit is locked out
35
Unit is locked out due to low voltage on the 24 VAC supply
36
Smoke Purge
37
Duct Static has Exceeded Limit
38
Supply Air Temperature Cooling
39
Supply Air Temperature Heating
40
Economizer Minimum Position
41
Space Temperature
42
Faulty Duct Static Pressure Sensor / Low Reading
43
Freeze Stat Trip