Table 29: Flash Codes for the Gas Heat Ignition Control Board

Flash Code

Description

Technician Corrective Action

Heartbeat

Normal Operation - no staus or error information 

currently needs to be displayed

Steady Off

No Power to Control - 24v AC is not present to the 

control's 24VAC and C terminals.                         

Alternately: The control has catastrophic damage that will 

not allow the LED display - It is likely that there will be 

visible physical evidence of the damage 

Verify line voltage is present at the primary of the 75VA transformer, verify 24v 

AC is present at the secondary of the 75VA transformer. Verify 24v AC is 

present from the Simplicity Lite control's C to SD terminals indicating the 3.2A 

control circuit breaker and phase monitor contacts are closed. Verify 24v AC is 

present from the ignition control's C to 24VAC terminals indicating the 

Simplicity Lite to Ignition control wiring is intact.

Steady On

The Control's Microprocessor Has Not Passed its Self-

check

Cycle power to the control to eliminate the possibility that transient voltage 

conditions such as surges, brownouts, etc. have not created a false indication. 

If the steady on LED indication repeats, the control will need to be replaced and 

potential causes for failure, such as excessive voltage, RF interference, etc. 

should be investigated.

2 Flashes

The Induced Draft Pressure Switch is Stuck Closed - 24v 

AC is received to the control's PS terminal at the same 

time as 24v AC to initiate heating operation is received at 

the control's W1 terminal

Verify that the induced draft pressure switch contacts are not stuck or welded 

closed. Verify that the ignition control's INDUCER contacts are not stuck or 

welded closed causing the induced draft motor to run continuously. Verify that 

the wiring from the ignition control's W1 terminal through the induced draft 

pressure switch and rollout switch to the ignition control's PS terminal is not 

shorted.

3 Flashes

The Induced Draft Pressure Switch Did Not Close - 24v 

AC was not received to the control's PS terminal within 5 

seconds of the ignition control energizing the induced 

draft motor or 24v AC was later lost to the control's PS 

terminal while the ignition control energized the induced 

draft motor

Verify that the induced draft motor is operable, the ignition control's INDUCER 

contacts are not open, the induced draft blower wheel is intact and there are no 

blockages in the combustion air / induced draft path. Verify that the induced 

draft pressure switch sensing tubing is intact. With an incline manometer, digital 

manometer or Magnehelic® gauge teed into the pressure switch sensing line 

verify that the negative pressure exceeds the setting listed on the induced draft 

pressure switch label and the switch's contacts correctly close at the setting 

listed 

4 Flashes

Open Limit - 24v AC has been lost to the control's L 

terminal

Verify proper gas manifold pressure. Correct the inadequate indoor airflow 

condition. Verify filters, indoor coil and blower wheel are clean. Verify that the 

blower belt is properly maintained and adjusted; the blower contactor and 

motor are operable and wheel has the correct rotation. Verify that the ducting is 

not restrictive. Verify indoor air volume is at least the minimum required for the 

heat section by measuring the indoor coil pressure drop and comparing the 

reading to the chart in the Installation Manual. Verify heating mode blower on/

off delays are proper for the heat type and provide adequate heat section 

cooling at the termination of the heating cycle. Verify wiring for main and 

auxiliary limits is intact

5 Flashes

Flame has been sensed when the MV1 output is off, or 
24v AC is present at the MV1 output without 24v AC to 

the W1 input, or 24v AC is present at the MV2 output 

without 24v AC at the MV1 output

Verify that the gas valve is not slow to shut off, leaks by or otherwise does not 
completely shut off gas flow when de-energized. Verify gas valve wiring to the 

control's MV1 and MV2 terminals is intact and not shorted in a manner that 

would improperly allow 24v AC from another circuit to be applied to the 

control's MV1 or MV2 terminals. Verify the control's contacts for MV1 and MV2 

outputs are not shorted.  

6 Flashes

Ignition lockout - A flame signal of 1.0

μ

a or greater could 

not be established in 3 attempts for ignition at the 

initiation of the heating cycle / or / the flame signal has 

dropped below 1.0

μ

a 5 times during the heating cycle

Verify that combustion air openings are without blockages and that the unit has 
proper clearance to the structure and adjacent units .Verify that the burners are 

clean and without blockages that could interfere with gas flow. Verify that the 

ignitor sparks with an 

1/8" gap to the crossover area of the left burner. Verify 

that the flame sensor is intact and positioned with an 

1/8" gap to the right 

burner. Verify that the gas lines have been purged of air and proper gas inlet 
pressure. Verify that the gas valve is opening and adjusted to provide proper 

manifold pressure. Verify that the wiring to the gas valve is intact. Verify that 

there is no wind, rain or snow entering the heat compartment to interfere with 

ignition or the burners. Verify that there are no conditioned air leaks or heat 

exchanger breaches to interfere with ignition or the burners 

Содержание ZR Series

Страница 1: ...tion 40 17 ZR037 061 Bottom Duct Application 41 18 RPM Selection 42 19 Indoor Blower Specifications 42 20 Power Exhaust Specifications 42 21 Motor Sheave Datum Diameters 44 22 Additional Static Resist...

Страница 2: ...est edition Wear safety glasses and work gloves Use quenching cloth and have a fire extinguisher available during brazing operations Improper installation may create a condition where the operation of...

Страница 3: ...combustible flooring or in the U S on wood flooring or Class A Class B or Class C roof covering materials 4 For use with natural gas convertible to LP with kit This product must be installed in strict...

Страница 4: ...is not listed above ZZ will be assigned and configuration options will be located in digits 15 18 Two Stage Natural Gas Heat Options A05 49 MBH Output Aluminized Steel Single Stage 037 049 A07 65 MBH...

Страница 5: ...Bracket 2 Turn each bracket toward the ground and the protective plywood covering will drop to the ground 3 Remove the condenser coil external protective covering prior to operation 4 Remove the tool...

Страница 6: ...n to 0 F when this product is applied in a comfort cooling application for people An economizer is typically included in this type of application When applying this product for process cooling applica...

Страница 7: ...g until the unit is near the place of installation Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars whose length exceeds the largest dimens...

Страница 8: ...ght lbs Center of Gravity 4 Point Load Location lbs 6 Point Load Location lbs Shipping Operating X Y A B C D A B C D E F 037 3 ZR 887 867 40 3 25 5 205 170 223 269 141 124 110 144 163 185 049 4 ZR 900...

Страница 9: ...Johnson Controls Unitary Products 9 Figure 8 ZR037 Physical Dimensions 25 31 59 00 15 51 29 75 59 LEFT 11 3 8 21 3 16 89 27 5 16 4 3 16 FRONT See detail A for gas inlet A See detail B for drain locati...

Страница 10: ...Controls Unitary Products Figure 9 ZR049 061 Physical Dimensions 24 47 TYP 2 PL 15 38 15 38 59 00 15 25 29 69 59 LEFT 11 3 8 21 3 16 89 27 5 16 4 3 16 FRONT See detail A for gas inlet A See detail B...

Страница 11: ...3 16 15 3 16 6 3 16 42 CABINET 3 126 2 000 3 184 4 727 7 705 14 594 Gas Pipe Inlet Gas Exhaust Vent 5 3 8 3 4 FPT Table 5 ZR037 061 Unit Clearances Direction Distance in Direction Distance in Top1 1 U...

Страница 12: ...nit Bottom Duct Openings Bottom condensate drain Bottom gas supply entry FRONT RETURN AIR SUPPLY AIR RIGHT LEFT 20 1 8 19 1 8 17 1 8 6 13 16 6 13 16 32 11 16 14 1 2 16 3 8 18 1 16 25 9 16 12 5 16 27 1...

Страница 13: ...Cover Power Entry 2 1 2 Control Entry 7 8 Power Entry 2 1 2 Convenience Outlet Cover Convenience Outlet Power Entry 7 8 FRONT Dot Plugs 5 5 32 31 11 16 2 31 32 18 1 4 Return Air Supply Air A B C D Ta...

Страница 14: ...ary Products Figure 13 ZR037 061 Unit Left Duct Opening Figure 14 ZR037 061 Roof Curb 4 5 16 30 3 8 8 or 14 50 1 2 30 20 20 80 5 8 6 2 TYP INSULATED DECK UNDER COMPRESSOR SECTION INSULATED DECK UNDER...

Страница 15: ...bottom duct application no duct cover changes are necessary For side duct application remove the side duct covers and install over the bottom duct openings The panels removed from the side duct conne...

Страница 16: ...ing must conform to local codes Use a sealing compound on male pipe threads Install condensate drain line from the 3 4 inch NPT female connection on the unit to an open drain Figure 20 Condensate Drai...

Страница 17: ...cement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire A disconnect must be utilized for these units Factory installed disconnects are available If...

Страница 18: ...the unit nameplate Refer to Electrical Data Table 8 to size power wiring fuses and disconnect switch Power wiring is brought into the unit through the side of the unit or the basepan inside the curb F...

Страница 19: ...Wire Sizes Wire Size Maximum Length1 1 From the unit to the thermostat and back to the unit 18 AWG 150 Feet OCC C RC G Y2 Y1 W2 W1 X R THERMOSTAT TERMINALS CONTROL TERMINAL BLOCK TERMINALS ON A LIMITE...

Страница 20: ...2 41 6 58 5 65 4 60 70 230 11 9 88 0 18 5 2 1 5 2 5 5 0 0 None 24 3 29 8 35 40 E06 6 0 1 14 4 24 5 31 4 35 40 E08 9 0 1 21 7 33 6 40 4 35 45 E15 15 0 2 36 1 51 6 58 5 60 60 E20 20 0 2 48 1 66 6 73 5...

Страница 21: ...8 1 18 9 30 1 37 0 35 40 E15 11 3 2 31 4 45 7 52 6 50 60 E20 15 0 2 41 6 58 5 65 4 60 70 230 11 9 88 0 18 5 2 1 5 2 5 5 0 0 None 24 3 29 8 35 40 E06 6 0 1 14 4 24 5 31 4 35 40 E08 9 0 1 21 7 33 6 40...

Страница 22: ...1 18 9 42 6 49 5 45 50 E15 11 3 2 31 4 58 2 65 1 60 70 E20 15 0 2 41 6 71 0 77 9 80 80 230 11 9 88 0 18 5 2 1 5 2 5 5 10 0 None 34 3 39 8 45 50 E06 6 0 1 14 4 37 0 43 9 45 50 E08 9 0 1 21 7 46 1 52 9...

Страница 23: ...1 18 9 42 6 49 5 45 50 E15 11 3 2 31 4 58 2 65 1 60 70 E20 15 0 2 41 6 71 0 77 9 80 80 230 11 9 88 0 18 5 2 1 5 2 5 5 10 0 None 34 3 39 8 45 50 E06 6 0 1 14 4 37 0 43 9 45 50 E08 9 0 1 21 7 46 1 52 9...

Страница 24: ...ges 1 1 1 1 1 1 1 1 1 Temperature Rise Range F 20 50 F 25 65 F 35 80 F 20 50 F 25 65 F 35 80 F 25 65 F 35 80 F 45 75 F Gas Limit Setting F 200 F 235 F 290 F 200 F 235 F 290 F 235 F 290 F 240 F Gas pip...

Страница 25: ...12 x 9 12 x 9 12 x 9 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44 Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59 Belt A47 A47 A47 A47 A47 A47 Motor HP each 1...

Страница 26: ...2 22 22 22 22 Temperature Rise Range F 20 50 F 25 65 F 35 80 F 20 50 F 25 65 F 35 80 F 25 65 F 35 80 F 45 75 F Gas Limit Setting F 200 F 235 F 290 F 200 F 235 F 290 F 235 F 290 F 240 F Gas piping conn...

Страница 27: ...2 x 9 12 x 9 12 x 9 Type Centrifugal Centrifugal Centrifugal Motor Sheave 1VP34 1VL44 1VP34 1VL44 1VP34 1VL44 Blower Sheave AK61 AK59 AK61 AK59 AK61 AK59 Belt A47 A47 A47 A47 A47 A47 Motor HP each 1 1...

Страница 28: ...with the local gas utility Figure 23 Side Entry Gas Piping NOTE Routing of gas piping must not interfere with the flue or heat compartment access Figure 24 Bottom Entry Gas Piping NOTE Maximum capacit...

Страница 29: ...mbers 1NP0454 or 1NP0455 All LP gas equipment must conform to the safety standards of the National Fire Protection Association Table 12 Gas Heat Minimum Supply Air Size Tons Model Heat Size Supply Air...

Страница 30: ...at least once a year For specific troubleshooting and maintenance procedures please refer to the smoke detector s installation instructions which accompanies the unit Motorized Outdoor Damper The Moto...

Страница 31: ...ly fan system both set points should be set to the same value Free Cooling Four types of free cooling options are available dry bulb changeover single enthalpy dual enthalpy changeover and Auto Dry Bu...

Страница 32: ...one stage of cooling If the economizer output goes to minimum position and the SAT is less than Economizer Setpoint 1 F the control starts a 12 minute timer to de energize a compressor output If at an...

Страница 33: ...r actuator position feedback Connects through circuit trace to 24V IN pin HOT C COM Mixed Air Temperature sensor input from 10K 77 F Type III negative temperature coefficient thermistor MAT parameter...

Страница 34: ...FType selection is Modulating Damper Used to ramp the power exhaust fan VFD position the discharge damper actuator COM 24 VAC common 0 10 VDC negative for the power exhaust variable frequency drive di...

Страница 35: ...e Indoor Air Quality sensor IAQRange parameter sets the CO2 parts per million measured by the indoor air quality sensor when it outputs 10 VDC IAQ parameter reports input status 0 5000ppm Used for dem...

Страница 36: ...n proper rotation Blower Rotation Check for proper supply air blower rotation If the blower is rotating backwards the line voltage at the unit point of power connection is misphased See PHASING R 24V...

Страница 37: ...ensity of the air However since the air at high altitude is less dense less static pressure will be generated and less power will be required than a similar application at sea level Air density correc...

Страница 38: ...iven is at an elevation of 5 000 ft The first step is to convert this static pressure to equivalent sea level conditions Sea level static pressure 1 5 832 1 80 Enter the blower table at 6000 sCFM and...

Страница 39: ...or and drive 5 turns open will achieve 1230 RPM Example Supply Air Blower Performance Air Flow CFM Available External Static Pressure IWG 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 RPM BHP RPM BHP RPM BH...

Страница 40: ...27 0 5 719 0 6 801 0 6 876 0 7 943 0 8 1005 0 9 1063 1 0 1117 1 1 1169 1 2 1400 537 0 5 639 0 5 731 0 6 813 0 7 888 0 7 955 0 8 1017 0 9 1075 1 0 1129 1 1 1181 1 2 1500 549 0 5 650 0 6 742 0 6 824 0 7...

Страница 41: ...0 8 942 0 8 994 0 9 1046 1 0 1100 1 2 1157 1 3 1400 617 0 5 705 0 6 781 0 6 847 0 7 907 0 8 962 0 9 1014 1 0 1066 1 1 1119 1 2 1177 1 3 1500 637 0 6 724 0 6 800 0 7 867 0 8 927 0 8 981 0 9 1034 1 0 1...

Страница 42: ...ection Size Tons Model Airflow Option HP Max BHP Motor Sheave Blower Sheave 6 Turns Open 5 Turns Open 4 Turns Open 3 Turns Open 2 Turns Open 1 Turn Open Fully Closed 037 3 0 ZR Std 1 5 1 5 1VP34 AK61...

Страница 43: ...ble motor sheave is open 5 Select the correct blower performance table for the unit from Tables and 17 Tables are presented for side and downflow configuration 6 Determine the unit Measured CFM from t...

Страница 44: ...allation errors leaks or undesirable systems effects that can result in loss of airflow Even small changes in blower speed can result in substantial changes in static pressure and BHP BHP and AMP draw...

Страница 45: ...02 0 03 0 01 0 01 0 01 0 02 0 02 0 02 1200 0 04 0 00 0 04 0 01 0 01 0 01 0 02 0 02 0 02 1300 0 03 0 01 0 05 0 01 0 01 0 01 0 03 0 03 0 03 1400 0 03 0 03 0 07 0 02 0 02 0 02 0 03 0 03 0 03 1500 0 03 0...

Страница 46: ...he AUTO position and drives the economizer dampers from fully closed to their minimum position If the enthalpy of the outdoor air is below the setpoint of the enthalpy controller previously determined...

Страница 47: ...B will not lockout the compressor due to a freezestat trip However a freezestat trip will de energize the compressor If the call for cooling is still present at the end of the ASCD and the freezestat...

Страница 48: ...On Reheat Compressor K No Reheat w Reheat Y1 Call for Cooling is Y1 Call for Cooling Calling Y2 Call for Cooling De calling or not calling Y2 Call for Cooling is Y1 is Calling for Cooling is notcalli...

Страница 49: ...il Condensing coil 1 and the Reheat coil are active and the condensing coil 2 is inactive Refrigerant Recovery Valve 2 Sol 2 is opened allowing refrigerant to return to the active system Refrigerant R...

Страница 50: ...ed by inadequate supply air flow occurs thus shutting down the heater and energizing the blower Reset Remove the call for heating by lowering the thermostat setting lower than the conditioned space te...

Страница 51: ...unit fails after three ignition attempts the furnace is locked out for one hour The furnace is monitored during this one hour period for unsafe conditions Recycle Operation When a flame is lost after...

Страница 52: ...the pressure switch opens for 2 seconds the GV will be de energized the ignition cycle is aborted and the ICB flashes the appropriate code See Table 29 Ignition Control Flash Codes The draft motor is...

Страница 53: ...Check for correct manifold gas pressures See CHECKING GAS INPUT 3 Check the supply gas pressure It must be within the limits shown on the rating nameplate Supply pressure should be checked with all g...

Страница 54: ...bic foot test dial 5 Using the number of seconds it takes for one revolution of the dial calculate the cubic feet of gas consumed per hour See example below 6 If necessary adjust the low pressure regu...

Страница 55: ...unit on first stage 9 Once pressure has been checked replace the plastic cap covering the HI and LO pressure adjustment screws NOTE When using natural gas the manifold pressure for second stage 100 i...

Страница 56: ...nstallation and operation guides are located on www upgnet com under Product Center Equipment Catalog Commercial Products Zoning Systems and Controls 1 Local LCD on Unit Control Board 2 Mobile Access...

Страница 57: ...the cursor is on the top Status line hit the ENTER button This action steps the LCD display into the status mode Hit ENTER to view the status menu Press Enter Step 2 Scroll down to DVent Mode This is...

Страница 58: ...aged ENTER CANCEL JOY C PWR 7 7 77 Clg Engaged LeadLag Engaged Press Enter Joy Stick Down 2 Step 6 By toggling down 4 times the screen reaches the ClgOcc SP screen or Cooling Occupied Set Point ENTER...

Страница 59: ...microprocessor connects through circuit trace to the SD 24 terminal SD 24 24 VAC hot out for factory accessory smoke detector condensate overflow and or user shutdown relay switching in series Connec...

Страница 60: ...Lit indicates 24 VAC is present at C and 24V terminals FAULT Red hard lockout networking error and firmware error indicator 1 2 second on off flashing indicates one or more alarm is currently active 1...

Страница 61: ...tor Input required for operation of 2 compressor units not active for 1 compressor units 3 625 VDC reading EC2 to EC2 with open circuit Used in suction line temperature safety Pinned connections on ri...

Страница 62: ...reheat components Effective only for reheat units output with reheat operation FAN 24 VAC hot output for indoor blower contactor coil indoor blower VFD enable relay coil Output with heat cool operati...

Страница 63: ...nter of the board Positive of the 15 VDC reading to C circuit for powering an optional netstat and or Multi Touch gateway C Common for SA BUS power and communication circuits Also incorporated in the...

Страница 64: ...BUS BACnet MSTP communication circuit Earth ground reference of the cable to prevent interference on the FC bus BACnet MSTP communication circuit Item Selector in red housing at left on top edge of t...

Страница 65: ...incline manometer digital manometer or Magnehelic gauge teed into the pressure switch sensing line verify that the negative pressure exceeds the setting listed on the induced draft pressure switch la...

Страница 66: ...16 6 7 95 171 71 383 102 14 7 3 400 Cfm Ton 75 63 75 138 62 288 82 21 6 3 85 141 62 321 90 20 6 7 95 144 61 372 98 18 7 2 Table 31 ZR049 Charging Table Air Flow Indoor Db Wb Outdoor DB Suction Pressu...

Страница 67: ...102 22 11 4 300 Cfm Ton 80 72 75 151 72 278 84 20 9 6 85 156 71 309 93 19 10 3 95 162 69 354 102 18 11 5 300 Cfm Ton 75 63 75 131 58 279 87 24 9 8 85 135 58 300 92 22 10 1 95 140 56 347 100 21 11 2 4...

Страница 68: ...up This confidence is supported by the 30 day dealer protection coverage portion of our standard warranty policy which states that Johnson Controls UPG will cover parts and labor on new equipment star...

Страница 69: ...full open position and the frequency drive is operating at 60 HZ Do not proceed with the equipment start up without the design CFM information Design Supply Air CFM __________________________ Design...

Страница 70: ...omplete Air Moving Inspection Completed See Notes Alignment of drive components Belt tension adjusted properly Blower pulleys tight on shaft bearing set screws tight wheel tight to shaft Pressure swit...

Страница 71: ...to increase of decrease the airflow to meet the design conditions If the motor pulley size was changed measure the outside diameters of the motor and blower pulleys and record those diameters here Bl...

Страница 72: ...Return Air Temperature ________________ F db ________________ F wb ________________ RH Mixed Air Temperature ________________ F db ________________ F wb ________________ RH Supply Air Temperature ____...

Страница 73: ...____________________________________________________________________ ________________________________________________________________________________________________________ __________________________...

Отзывы: