Physical data
Table 15: ZQ04 Physical Data
Models
Models
Component
ZQG04
ZQE04
Nominal Tonnage
3
3
Gross Capacity @ AHRI A point (Btu)
38,100
38,100
AHRI net capacity (Btu)
35,000
35,000
EER
12.2
12.2
SEER
14
14
IEER
-
-
Nominal CFM
1200
1200
System power (KW)
2.8
2.8
Refrigerant type
R-410A
R-410A
Refrigerant charge (lb-oz)
System 1
3-6
3-6
AHRI COOLING
PERFORMANCE
System 2
-
-
Heating Option
L
D
M
E
Heating Model
Low (Low-NOx)
Low
Med (Low-
NOx)
Med
1st. Stage Heat input (K Btu)
-
-
-
-
2nd. Stage Heat input (K Btu)
56
70
90
112
1st. Stage Heat output (K Btu)
-
-
-
-
2nd. Stage Heat output (K Btu)
45
56
72
90
AFUE %
-
-
-
81
FER Compliant
-
-
-
Yes
No. burners
2
2
3
3
No. stages
1
1
1
1
Temperature Rise Range (ºF)
10-40
20-50
35-65
50-80
Gas Limit Setting (ºF)
150
150
140
140
AHRI HEATING
PERFORMANCE
SINGLE PHASE
Gas piping connection (in.)
1/2
1/2
1/2
1/2
Heating Option
L
D
M
E
Heating Model
Low (Low-NOx)
Low
Med (Low-
NOx)
Med
1st. Stage Heat input (K Btu)
-
-
-
82
2nd. Stage Heat input (K Btu)
56
70
90
112
1st. Stage Heat output (K Btu)
-
-
-
66
2nd. Stage Heat output (K Btu)
45
56
72
90
Steady state efficiency (%)
80
80
80
80
No. burners
2
2
3
3
No. stages
1
1
1
2
Temperature Rise Range (ºF)
28-46
35-58
44-74
55-78
Gas Limit Setting (ºF)
150
150
140
140
AHRI HEATING
PERFORMANCE THREE PHASE
Gas piping connection (in.)
1/2
1/2
1/2
1/2
Length
74.1
74.1
Width
48.9
48.9
DIMENSIONS (in.)
Height
32.5
32.5
OPERATING WT. (lb)
498
450
Type
Scroll
Scroll
Quantity
1
1
COMPRESSORS
Unit Capacity Steps (%)
100
100
Face area (Sq. Ft.)
16.3
16.3
Rows
1
1
Fins per inch
23
23
Tube diameter (in./MM)
.63/16
.63/16
CONDENSER COIL DATA
Circuitry Type
2-pass Microchannel
2-pass Microchannel
INSTALLATION MANUAL ZQ SERIES 3 - 5 ton 60 Hertz R-410A
34
Johnson Controls Ducted Systems
Содержание ZQ Series
Страница 2: ...2 INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Страница 8: ...Nomenclature INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 8 Johnson Controls Ducted Systems ...
Страница 87: ...Start Up Sheet INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 87 Johnson Controls Ducted Systems ...
Страница 88: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 88 Johnson Controls Ducted Systems ...
Страница 89: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 89 Johnson Controls Ducted Systems ...
Страница 90: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 90 Johnson Controls Ducted Systems ...
Страница 91: ... INSTALLATION MANUAL ZQ SERIES 3 5 ton 60 Hertz R 410A 91 Johnson Controls Ducted Systems ...