<8. Detailed Data Setting>
8-7
IM 11M13A01-04E
In the example in Figure 8.2, the high alarm point is set to 7.5vol%O
2
, the delayed time is set to five
seconds, and hysteresis is set to 2vol%O
2
.
Alarm output actions in this figure are expressed as follows:
A. Although the oxygen concentration value exceeds the high limit alarm setpoint, it falls below the
high limit alarm setpoint before the preset delay time of five seconds elapses. So, no alarm is
issued.
B. The oxygen concentration value exceeds the high limit alarm setpoint and the delay time elapses
during that measurement. So, an alarm is issued.
C. Although the oxygen concentration value falls below the hysteresis set value, the value rises
again and exceeds the hysteresis set value before the preset delay time elapses. So, the alarm
is not canceled.
D. The oxygen concentration value falls below the hysteresis set value and the preset delay time
elapses, so the alarm is canceled.
8.4.3 Alarm Setting
Set the alarm setpoints following Table 8.7 listing parameter codes.
Table 8.7
Parameter Codes for Oxygen Concentration Alarms
Set item
Parameter code
Set value
Oxygen concentration
high-high alarm setpoint
D01
0-100%O
2
Oxygen concentration
high alarm setpoint
D02
0-100%O
2
Oxygen concentration
low alarm setpoint
D03
0-100%O
2
Oxygen concentration
low-low alarm setpoint
D04
0-100%O
2
Oxygen concentration
alarm hysteresis
D30
0-9.9%O
2
Delayed alarm action
D33
0-255 seconds
Oxygen concentration
high-high alarm detection
D41
0
Not detected
1
Detected
Oxygen concentration
high alarm detection
D42
0
Not detected
1
Detected
Oxygen concentration
low alarm detection
D43
0
Not detected
1
Detected
Oxygen concentration
low-low alarm detection
D44
0
Not detected
1
Detected
CAUTION
Even with alarms set, if “Not detected” has been set in the above alarm detection, no alarm is issued.
Be sure to set “Detected” in the above alarm detection if you use alarm features.
Содержание ZR202S
Страница 12: ...xi IM 11M13A01 04E Introduction ...
Страница 18: ...Blank Page ...
Страница 61: ...Blank Page ...
Страница 129: ...Blank Page ...
Страница 141: ...Blank Page ...
Страница 153: ......
Страница 155: ......
Страница 157: ......
Страница 159: ...Blank Page ...
Страница 160: ......
Страница 161: ......
Страница 162: ......
Страница 163: ......