![YOKOGAWA YTA Series Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/yokogawa/yta-series/yta-series_user-manual_3847593052.webp)
A-1
IM 01C50C05-01EN
Appendix1. ATEX Installation drawing YTA70PQA01
YTA70PQA01 20
21-04-21
1/2
ATEX
Installation drawing YTA70PQA01
For safe installation of theYTA70P
-
JA/V2S and YTA70P
-
JB/V2S the following must be observed.
The module shall only be Installed by qualified personnel who are familiar with the national and
international laws, directives and standards that apply to this area.
ATEX Certificate
DEKRA 14
ATEX0106X
Marking
Standards
EN IEC
60079
-
0:201
8
,
EN60079
-
11:2012
Non Hazardous Area
Hazardous area
Zone 0,
1,
2,
21, 22
II 1 G
Ex ia IIC
T6
…
T4
Ga
II 2
D Ex ia IIIC Db
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67
.2
mW
Lo: 35 mH
Co: 3.5
μ
F
Terminal:
11,12,13,14 and
21,22,23,24
Ui:
30
VDC
Ii
:
120
mA
Pi: 0.84 W
or Pi: 0.75 W
Li:
0
μ
H
Ci: 1
.0
nF
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67
.2
mW
Lo: 35 mH
Co: 3.5
μ
F
13
12
44
43
42
41
+
-
Barrier
23
22
54
53
52
51
+
-
Barrier
CH
2
CH
1
21
24
14
11
Ex HART
Communicator
R
R
250
<
R <
1100
ohm