3-4
IM 01B08D02-02EN
3.2 Setting
Sensor Type
Description
The sensor type can be set as for thermocouple and RTD cards.
Setting Details
Operation Display >
+ keys (to the Tuning Menu Display) >
+ keys (to
the Engineering Menu Display) > [
SC MAINT
] software key (Input Specification Setting
Display)
Engineering Display
Setting Procedure
(example of setting an RTD type)
(1) Press the [→] software key to display [SET INHB]
in highlight.
(2) Press the [ ] software key to display [SET ENBL].
(3) Press the [MNU] software key to display
01
MODEL
Directly input the card model (e.g., ER5*C)
(4) Press the [MNU] key several times to display
B00
SET
(5) Press the [PRM] software key several times to
display the left display.
(6) Press the [ ] or [ ] software keys to change the
data display section.
(7) Press the [ENT] software key to display the data
display section in highlight.
(8) Press the [ENT] software key again to accept the
setting.
Setting completed.
0502E.ai
Parameter
number
Parameter
name
Data display
Communication
status display
Software key
function display
Menu change key
Parameter change key
Cursor movement key
Data increase key
Data decease key
ENTER key