Thank you for purchasing the JUXTA Signal Conditioner.

Please read through this manual before use for correct handling.

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

http://www.yokogawa.com/ns/juxta/im/

You can download the latest manuals from the following website:

IM 77J01R21-01E

3rd Edition Feb. 2017 (YK)

CAUTIONARY NOTES FOR SAFE USE OF THE 

PRODUCT

This User’s Manual should be carefully read before installing and 

operating the product. Please keep this User’s Manual for future 

reference.

For more information of the safety precautions, please refer to the 

“Precautions on the Use of the JUXTA Series (IM 77J01A00-91Z1)”.

The related manuals and general specifications are shown in the 

table below.

Doc. Name

Doc. Number 

Precautions on the Use of the JUXTA Series (User’s Manual) IM 77J01A00-91Z1

Model VJRK Limit Alarm for RTD Input (User’s 

Manual)

IM 77J01R21-01E

(This manual)

Model VJRK Limit Alarm for RTD Input (General 

Specifications)

GS 77J01R21-01E

User’s manuals in the above table are essential parts of the 

product; keep it in a safe place for future reference.

This manual is intended for the following personnel;   

 •

Engineers responsible for installation, wiring, and maintenance 

of the equipment.

 • Personnel responsible for normal daily operation of the 

equipment.

The following symbol is used on the product and in this manual to 

ensure safe usage.

 WARNING

Calls attention to actions or conditions that could 

cause serious or fatal injury to the user, and indicates 

precautions that should be taken to prevent such 

occurrences.

 CAUTION

Calls attention to actions or conditions that could 

cause injury to the user or damage to the instrument 

or property and indicates precautions that should be 

taken to prevent such occurrences.

CHECKING THE PRODUCT SPECIFICATIONS 

AND THE CONTENTS OF THE PACKAGE

(1) Model and Specifications Check

  Check that the model and specifications indicated on the 

nameplate attached to the side face of the main unit are as 

ordered. 

(2) Contents of the Package

  Check that the package contains the following items: 

 •

VJRK: 1 

  Standard Accessories: 

 •

Tag number label: 1 sheet

 •

Range label: 1 sheet

 •

User’s manual (IM 77J01R21-01E, this manual): 1 copy

 •

User’s manual (IM 77J01A00-91Z1): 1 copy

GENERAL

This plug-in type Limit Alarm for RTD input receives RTD signal.

 • Each parameter setting can be changed using a PC (VJ77 PC-

based Parameters Setting Tool) or the Handy Terminal (JHT200 ).

MODEL AND SUFFIX CODES

Model

Suffix codes

Description

VJRK

-0 2

x -x

T 0 0

/x

Limit Alarm for RTD Input

Fixed 

code

-0

Always -0

Output 

configuration

2

2 outputs

Power supply

6

100-240 V AC/DC

*1

7

15-30 V DC

*2

Input signal

-1

Pt100 (ITS-90)

-2

JPt100 (JIS'89)

-3

Pt50 (JIS'81)

-4

Pt100 (IPTS-68)

Output signal

T

Alarm output (2 relay contacts)

Fixed code

0

Always 0

Fixed code

0

Always 0

Option

/SN

No socket (with socket if not specified)

/C0

HumiSeal coating

/FB

Fuse bypass

/DF

Fahrenheit display function

*1: Operating range: 85 to 264V AC/DC

*2: Operating range: 12 to 36V DC

*3: DC voltage signal or DC current signal

1.  MOUNTING METHODS 

 

CAUTION

 

Plug/disconnect the main unit into/from the 

socket vertically to the socket face.  Otherwise the 

terminals may bend and it may cause bad contact.

 

The converter shall not tilt 5 degrees or more in 

either direction when installed.

 

When the converter is not connected to the socket,  

it is necessary to protect the socket against ingress 

of dust to the connector part.

 

Keep this product in a conductive bag when 

plugged out, during transport or storage.

1.1  Wall Mounting 

Loosen the main unit-fixing screw to disconnect the main unit 

from the socket.  Next, anchor the socket onto the wall with 

screws. Then, plug the main unit into the socket and secure the 

main unit with the main unit-fixing screw. 

Main

unit-fixing

screw

Socket

Main unit

Hole for main 

unit-fixing screw

Mounting

screws

<Mounting Dimensions>

Unit: mm

29.5 or more

22±0.2

59±0.3

2-M4 or 

2-ø4.5 or more

Model VJRK

Limit Alarm  

for RTD Input