
3-16
IM 05P07A01-01EN
66 Random reading
Function
The register data of register Nos. specified at random is read.
• Register Nos. can be specified from all register areas.
• The maximum number of registers that can be set is 100.
• For details on the response format at an error, see “
● Response in an error state
” in
“3.1.3 Configuration of Responses (response from UTAdvanced).”
Message (during normal operation)
Element
Message start
mark (:)
Address No.
(ADRS)
Function code
(0x42)
Number of
specified
registers
Byte count
(Note 1)
Number of bytes in RTU mode
None
1
1
2
1
Number of bytes in ASCII
mode
1
2
2
4
2
Continuation of message
Specified
Register No.
• • •
Specified
Register No
Error check
Message
end mark
(CR+LF)
2
• • •
2
2
None
4
• • •
4
2
2
Response (during normal operation)
Element
Message start
mark (:)
Address No.
(ADRS)
Function code
(0x42)
Byte count
(Note 1)
Register
conten
• • •
Number of bytes in RTU mode
None
1
1
1
2
• • •
Number of bytes in ASCII
mode
1
2
2
2
4
• • •
Continuation of response
Register
content
Error check
Message end
mark (CR+LF)
2
2
None
4
2
2
Note 1: Byte count = 2 x number of read registers
3.1 Modbus Communication
Содержание UTAdvanced Series
Страница 17: ...Blank Page...
Страница 77: ...Blank Page...
Страница 285: ...Blank Page...
Страница 325: ...Blank Page...
Страница 467: ...Blank Page...
Страница 557: ...Blank Page...
Страница 825: ...Blank Page...
Страница 861: ...Blank Page...
Страница 863: ...Blank Page...
Страница 865: ...Blank Page...