1
IM05C01E12-01E
30
°
(MAX)
■
Checking Package Contents
Before using the product, check that its model & suffix codes are as you ordered.
Check the package contents against the list below.
• Temperature controller
• Mounting bracket
• User’s manual (this manual)
1
1 for UT150
2 for UT152, UT155
1
..........................
................................
...................
Model
Model and Suffix Codes
Suffix code
Description
UT150
UT152
UT155
Temperature controller
–R
–V
–A
Relay output (time-proportional PID or on/off control)
Voltage pulse output (time-proportional PID)
4 to 20mA output (continuous PID)
N
R
V
A
No cooling output (standard type)
Relay output (time-proportional PID or on/off control)
Voltage pulse output (time-proportional PID)
4 to 20mA output (continuous PID)
Option
/AL
/HBA
/EX
/RET
/RS
/V24
Alarm outputs (2 points)
Heater disconnection alarm (includes optional /AL function)
SP1/SP2 switching, starting of timer, and RUN/STOP
switching by external contacts
PV retransmission output in 4 to 20mA
Communication function
Power Supply 24V DC / 24V AC
Control output for standard-
type (or for heating)
Control output for cooling
Note:When specifying the /RS option, be sure to order the required number of copies of
Communication Functions User’s Manual separeately.
The following safety symbol is used both on the product and in this user’s manual.
This symbol stands for “Handle with Care.” When displayed on the product, the operator should
refer to the corresponding explanation given in the user’s manual in order to avoid injury or death
of personnel and/or damage to the product. In the manual the symbol is accompanied by an expla-
nation of the special care that is required to avoid shock or other dangers that may result in injury
or loss of life.
The following symbols are used in this manual only.
NOTE
Indicates that operating the hardware or software in a particular manner may lead to
damage or result in system failure.
IMPORTANT
Draws attention to information that is essential for understanding the operation and/or
features of the product.
■
Exemption from Responsibility
Make sure that all of the precautions are strictly adhered to. Yokogawa Electric Corporation assumes no liability
for any damage resulting from use of the instrument in contradiction to the precautions.
Also, Yokogawa Electric Corporation assumes no liability to any party for any loss or damage, direct or indirect,
caused by the use or any unpredictable defect of the instrument.
CAUTION
To prevent electric shock, the source of power to the controller must be turned off when mounting the controller
on to a panel.
NOTE
To install the controller, select a location where:
1. No-one may accidentally touch the terminals;
6. There are no resulting magnetic disturbances;
2. Mechanical vibrations are minimal;
7. The terminal board (reference junction compen-
3. Corrosive gas is minimal;
sation element, etc.) is protected from wind;
4. The temperature can be maintained at about 23
°
C with
8. There is no splashing of water; and
minimal fluctuation;
9. There are no flammable materials.
5. There is no direct heat radiation;
Never place the controller directly on flammable items.
If the controller has to be installed close to flammable items or equipment, be
sure to enclose the controller in shielding panels positioned at least 150mm
away from each side. These panels should be made of either 1.43mm thick
metal-plated steel plates or 1.6mm thick uncoated steel plates.
●
Mount the controller at an angle within 30
°
from horizontal with
the screen facing upward. Do not mount it facing downward.
a.
b.
g.
UT152
UT155
UT150
h.
e.
d.
c.
f.
a.
b.
f.
g.
e.
c.
d.
h.
f.
c.
d.
h.
a.
e.
b.
g.
150mm
150mm
150mm
150mm
a.
PV display (red)
Indicates PV (measured value) and character information such as parameter codes and error codes.
b.
SP display (green)
Indicates SP (target setpoint) and parameter values.
c.
Alarm 1 (AL1) lamp (red)
Lit when alarm 1 is activated.
d.
Alarm 2 (AL2) lamp (red)
Lit when alarm 2 is activated.
e.
SP2 lamp (green)
Lit when SP2 is being used for control operation.
f.
Output (OUT) display lamps
UT150: (Left: orange; right: green)
UT152, UT155:
(Upper: orange; lower: green)
Lit while control output is being output.
• The left (upper) lamp is lit in orange during control output of standard type.
• In heating/cooling control, the left (upper) lamp lights up in orange when the heating-side output
is active; while the right (lower) lamp lights up in green when the cooling-side output is active.
g.
Data change keys
(Indicated as simply the and
keys hereafter.)
• Changes SP and the parameter values.
• Pressing the key decreases the data value and pressing the key increases
it. Holding down the key will gradually increase the speed of the change.
h.
SET/ENT key (data registering key)
(Indicated as simply the key
hereafter.)
• Registers the data value changed using the data change keys.
• Switches between operating display or parameter setting displays sequentially.
• Pressing the key for 3 seconds or longer in the operating display retrieves the
operating parameter setting display.
• Pressing the key for 3 seconds or longer in either an operating or setup parameter
setting display transfers back to operating display 1. (See page 3.)
Name
Function
NOTE
Splash-proof construction is not available when the side-by-side close mounting method shown in the above
figures, is chosen for any of the controllers.
max. 91.8
96
1-1051-6041-5031-4021-3011-20
min. 117
min. 1
4
5
92
+ 0.8
0
92
+ 0.8
0
25
53
+0.8
0
92
2. Side-by-side Close Mounting
1. General Mounting
96
11
100
max. 91.8
max. 1
1
2
Panel thickness
1 to 10
Unit: mm
UT155
N is the number of controllers.
If N > 5, then measure the actual length.
[(N –1)
×
96
+
92]
+0.8
0
1-1021-301-20
min. 70
48
min. 145
92
+0.8 0
45
+0.6
0
max. 4
4
.6
max. 9
1
.8
max. 1
1
2
100
96
Panel thickness
1 to 10
11
25
53
+0.8
0
92
2. Side-by-side Close Mounting
1. General Mounting
Unit: mm
UT152
N is the number of controllers.
If N > 5, then measure the actual length.
[(N –1)
×
48
+
45]
+0.6
0
max. 61
Panel thickness
max. 47.8
max. 44.8
max. 44.8
100
12
48
48
1 to 10
Unit: mm
UT150
1. General Mounting
min. 70
min. 70
45
+0.6
0
45
+0.6
0
25
25
[(N –1)
×
48
+
45]
+0.6
0
+0.6
0
45
2. Side-by-side Close Mounting
N is the number of controllers.
If N > 5, then measure the actual length.
■
Mounting the Controller
UT152, UT155
UT150
Insert a screwdriver
into the brackets to
tighten the screws.
Large bracket
(top)
Terminal board
Panel
Small bracket
(bottom)
Direction for mounting
Insert the controller into the opening with the terminal board facing the front.
Set and tighten the top and bottom brackets on the controller to fix it on the
panel.
1. Affix the bracket over the back
end of the controller.
2. Push the bracket to the panel,
and then secure the bracket
into position.
Panel
Bracket
UT150
[ How to remove the bracket ]
To move the bracket, push down the center of the upper and lower parts
of the controller softly. The bracket is released from the latch.
User’s
Manual
IM 05C01E12-01E
Jun. 2004 3rd Edition
Please read through this user's manual to ensure correct usage of the controller and keep it handy for
quick reference.
Models
UT150, UT152, UT155
Temperature Controller
1. Notice
2. What is on the Front Panel?
3. Installing the Controller
4. Panel Cutout Dimensions and External Dimensions
5. Wiring
6. Hardware Specifications
7. Key Operations
8. Troubleshooting
........................................................... 1
................................. 1
...................................... 1
..... 1
.......................................................... 2
..................................... 2
................................................ 3
............................................... 3
Contents
Revision Record
IM 05C01E12-01E 1st Edition: Oct. ’00
2nd Edition: Feb. ’01
3rd Edition: Jun. ’04
1. Notice
2. What is on the Front Panel ?
3. Installing the Controller
4. Panel Cutout Dimensions and External Dimensions