Monitoring and Control of Regular Operations
6
6.6 Selecting Target Setpoint Number (SPNO)
Setting Display
Parameter Setting Display
Operation Display >
PARAMETER
or
PARA
key for
3 seconds
(to [
MODE
] Menu Display) >
SET/ENTER
key (The setting
parameter is displayed.) >
Down arrow
key (The setting
parameter is displayed.)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SPNO.
SP number
selection
EASY
1 to 4 (Depends on the setup
parameter SPGR. setting.)
MODE
SPGR.
Number of SP
groups
STD
1 to 4
CTL
Description
The SP number (SPNO) selection can be used when the parameter ZON (zone PID
selection) is set to “SP group number selection.”
SP Group Number Selection
The PID group which is set in the PID number selection (PIDN) of each SP group is
used.
SP number (SPNO)
Target setpoint (SP)
Setting range of PID number
selection (PIDN)
1
SP
1 to 4
2
SP
1 to 4
3
SP
1 to 4
4
SP
1 to 4
When the SP parameter is displayed, the SP number is shown on Group display.
► Selection by contact input: 12.1 Setting Contact Input Function
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...