8-23
IM 05P01D31-01EN
Control Functions
8.3 Setting PID Control Mode (ALG)
Description
There are two PID control modes: standard PID control mode and fixed-point control
mode.
Select a PID control computation formula shown in the following table according to the
control mode or operation mode.
Operation mode
AUTO+Local
AUTO+Remote
Standard PID control
mode
PV derivative type
(output bump at SP change)
Deviation derivative type
Fixed-point control
mode
PV derivative type
(output bumpless at SP change)
PV derivative type
(output bump at SP change)
PV Derivative Type PID
This is a PID control method in which the derivative action works only on the PV.
It can also eliminate output bump due to SP changing operation in Local mode.
The following shows the PV derivative type PID control computation formula.
e
e
P
OUT
+
+
dt
Td
ΔPV
= 100
Ti
1
dt
d
∫
•
•
where OUT: control output, e: deviation (PV-SP), P: proportional band, Ti: integral time,
Td: derivative time, and ∆PV: PVn-PVn-1 (n-1: value before one control period)
PV Derivative Type PID (output bump at SP change)
SP
PV
OUT
PV Derivative Type PID (output bumpless at SP change)
SP
PV
OUT
8
Содержание UT Advanced UT32A
Страница 3: ......
Страница 21: ...Blank Page...
Страница 35: ...Blank Page...
Страница 45: ...Blank Page...
Страница 53: ...Blank Page...
Страница 89: ...Blank Page...
Страница 135: ...Blank Page...
Страница 143: ...Blank Page...
Страница 255: ...Blank Page...
Страница 333: ...App 4 IM 05P01D31 01EN Intentionally blank Appendix 1 Input and Output Table for Standard model...
Страница 334: ...App 5 IM 05P01D31 01EN Input and Output Table App Appendix 2 Input and Output Table for Detailed model See the next page...
Страница 337: ...Blank Page...
Страница 339: ...Blank Page...