<5.  Troubleshooting and Maintenance>

5-7

IM 05E01B02-41E

1st Edition : May 31,2000-00

5.2.4

Replacing Parts with a Limited Service Life

The following UP750 parts have a limited service life.
The service life given in the table assume that the controller is used under normal operating
conditions.

Part

Aluminum electrolytic condenser

Lithium battery for backup

About 10 years (rated)

About 10 years (rated)

Service life

Alarm output relays

About 100,000 more ON-OFF operations or with resistance load

Control output relays

About 100,000 more ON-OFF operations or with resistance load

If any of these parts, except control output relays, cause a controller failure due to deterio-
ration, contact your dealer for replacement at your cost.
Control output relays can be replaced by yourself.

SEE ALSO

“5.2.5  Replacing Control Output Relays,” for how to replace the control output relays.

Содержание UP750

Страница 1: ...Instruction Manual IM 05E01B02 41E Model UP750 Program Controller User s Manual for Single loop Control IM 05E01B02 41E 1st Edition...

Страница 2: ...Blank Page...

Страница 3: ...external contact inputs see 1 5 Terminal Wiring Diagrams 1 Installation 2 Initial Settings 3 Programming 3 5 Program Parameter Map 3 6 Lists of Program Parameter 4 Operations 6 1 Parameter Map 6 2 Li...

Страница 4: ...re to avoid electric shock or other dangers that may result in injury or loss of life The following symbols are used in the hardcopy user s manuals and in the user s manual supplied on the CD ROM NOTE...

Страница 5: ...Program Parameters 3 16 3 7 Program Pattern Setup Charts 3 21 3 8 Explanation of Program Functions 3 24 4 Operations 4 1 4 1 Monitoring purpose Operating Displays Available during Operation 4 1 4 2 P...

Страница 6: ...1 Cleaning 5 5 5 2 2 Replacing Brackets 5 5 5 2 3 Attaching Terminal Cover 5 5 5 2 4 Replacing Parts with a Limited Service Life 5 7 5 2 5 Replacing Control Output Relays 5 8 6 Parameters 6 1 6 1 Par...

Страница 7: ...ary analog input Note Note Not used in single loop control Check that the following items are provided Program controller of ordered model 1 Brackets mounting hardware 1 pair Unit label 1 User s Manua...

Страница 8: ...ed 9 no flammable materials are around Never place the controller directly on flammable items or equipment If the controller has to be installed close to flammable items or equipment be sure to provid...

Страница 9: ...min 0 8 0 0 8 0 92 0 8 0 92 0 8 0 92 N stands for the number of controllers to be installed However the measured value applies if N 5 100 11 UP750 General installation Side by side close installation...

Страница 10: ...front of the panel so that the terminal board on the rear is at the far side 2 Set the brackets in place on the top and bottom of the controller as shown in the figure below then tighten the screws of...

Страница 11: ...ance and cause no significant differences in resistance between the three wires The cables to be used for wiring terminal specifications and recommended parts are as shown below 3 Control output relay...

Страница 12: ...307 0 9 to 2 0 mm2 Thermocouple Shielded compensating lead wires JIS C 1610 X See Yokogawa Electric s GS 6B1U1 E RTD Shielded wires three conductors UL2482 Hitachi Cable Other signals Shielded wires R...

Страница 13: ...ance between three wires should be equal However 10 wire for a maximum range of 150 0 to 150 0 C Wire resistance effect 0 1 C 10 Allowable input voltage 10 V DC for thermocouple mV or RTD input 20 V D...

Страница 14: ...th the software Current output Single loop type terminals 16 17 heating side output terminals 16 17 cooling side output terminals 14 15 Number of outputs 1 or 2 two for heating cooling type switched b...

Страница 15: ...od 3 Contact Outputs Purpose Event output FAIL output and others Number of outputs 7 points Relay contact rating 240 V AC 1 A or 30 V DC 1 A Transistor contact rating 24 V DC 50 mA Display Specificati...

Страница 16: ...voltage of 100 to 240 V AC 10 50 60 Hz Power consumption Max 20 VA 8 0 W max Data backup Lithium cell with life expectancy of 10 years Withstanding voltage Between primary terminals and secondary term...

Страница 17: ...loop power supply Isolated from other input output terminals and internal circuit Relay contact control output terminals Isolated between contact output terminals and from other input output terminals...

Страница 18: ...1 ms Installation height Height above sea level of 2000 m or less Warm up time 30 minutes or more after power on Transportation and storage conditions Temperature 25 to 70 C Temperature change rate 20...

Страница 19: ...Installation 1 13 IM 05E01B02 41E 1st Edition May 31 2000 00 1 5 Terminal Wiring Diagrams NOTE Do not use unassigned terminals as relay terminals Terminal wiring diagrams are shown on and after the ne...

Страница 20: ...smission output 1 is not available if a 15 V DC loop power supply is used 14 15 Retransmission output 1 4 20 or 0 20 mA DC 14 15 15 V DC loop power supply 14 5 18 0 V DC 21 mA DC max Default 4 20 mA D...

Страница 21: ...tor contact rating 24 V DC 50 mA The functions of the external contact outputs are the defaults for single loop heating cooling control To change the functions reconfigure the Contact Output Registrat...

Страница 22: ...Blank Page...

Страница 23: ...mes This brings you to the display operating display that appears at power on Power on Set setup parameters See 2 2 Setting PV Input Type Setting First at Power on or 2 3 Changing PV Input Type Set th...

Страница 24: ...lit in green to indicate the status of operation or control PRG Is lit when in program mode RST Is lit when in reset mode HLD Is lit when in hold mode LOC Is lit when in local mode MAN1 Is lit when i...

Страница 25: ...1 Instrument input range 270 0 C 1370 0 C 0 0 C 800 0 C Maximum value of PV input range RH1 Minimum value of PV input scale SL1 1V 5V 0 0m 3 h 50 0m 3 h Maximum value of PV input scale SH1 2V 4V RL1 R...

Страница 26: ...OFF 3 Press the or key to display the required setpoint The figure below shows an example of setting a K type thermocouple 200 0 C to 500 0 C See Instrument Input Range Codes SET ENT PT No RUN RESET D...

Страница 27: ...range to 0 0 C SET ENT PT No RUN RESET DISP MODE MENU UPMD IN 4 changing input 1 range low RL1 0 0 Blinks during change 11 Press the SET ENT key once to register the setpoint SET ENT PT No RUN RESET...

Страница 28: ...a type E thermocouple W typeW 15 0 0 to 2300 0 C 32 to 4200 F 0 2 of instrument range 1 digit Platinel 2 Plati2 16 0 0 to 1390 0 C 32 0 to 2500 0 F 0 1 of instrument range 1 digit PR20 40 PR2040 17 0...

Страница 29: ...PV Input Range RL1 PV Input Decimal Point Position SDP1 Maximum Value of PV Input Scale SH1 or Minimum Value of PV Input Scale SL1 After a change has been made to any of these data items be sure to ve...

Страница 30: ...ited to explain the procedure 1st Edition May 31 2000 00 2 Press the SET ENT key for more than 3 seconds to call up the main menu PROG SET ENT PT No RUN RESET DISP MODE programming main menu PROG 3 Pr...

Страница 31: ...NT key once to display the parameter UNI1 SET ENT PT No RUN RESET DISP MODE SETUP MENU UPMD IN 2 input 1 unit select UNI1 C 12 Press the SET ENT key once to display the parameter RH1 maximum value of...

Страница 32: ...at power on figure below PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2 TME AL 1 1 2 3 4 MAN2 PRG RST HLD LOC MAN1 CAS PTNO 0 TM SEGNO 0 0 RCY 0 0 SP 0 0 C RST lamp ON 2 4 Setting Control Output T...

Страница 33: ...iguration UPMD 6 Press the SET ENT key once to display the submenu MD SET ENT PT No RUN RESET DISP MODE UP mode set SETUP sub menu MD 7 Press the key twice to display the submenu OUT SET ENT PT No RUN...

Страница 34: ...output type Heating side relay output terminals cooling side relay output terminals 1 2 3 Heating side pulse output terminals cooling side relay output terminals Heating side current output terminals...

Страница 35: ...3 seconds to call up the main menu PROG SET ENT PT No RUN RESET DISP MODE programming main menu PROG 3 Press the key once to display the main menu STUP SET ENT PT No RUN RESET DISP MODE password inpu...

Страница 36: ...uring change 10 Press the SET ENT key once The display momentarily becomes blank which is normal indicating the parameters have been initialized SET ENT PT No RUN RESET DISP MODE SETUP MENU UPMD OUT 1...

Страница 37: ...erature to 0 C in 10 minutes Event output Set a deviation of 5 C on both the positive and negative sides of a program setpoint to allow the controller to output an event signal if the temperature goes...

Страница 38: ...int SSP1 program parameter 7 Start code Setpoint of the Start Code STC program parameter 8 Final target setpoint Segment time Events PV event and Time event and Junction code Setpoint of each program...

Страница 39: ...Y2 on time of time event ON2 PV event setpoint PE2 off time of time event OFF2 Event number EV3 PV event type TY3 on time of time event ON3 PV event setpoint PE3 off time of time event OFF3 Event numb...

Страница 40: ...er for segment 1 Steps 17 to 25 configure the PV Event parameters EV1 TY1 and PE1 Step 28 configures the Final Target Setpoint TSP1 parameter for segment 2 not changed in this example Steps 29 to 31 c...

Страница 41: ...DISP MODE MENU PROG PRG 3 start set point 1 SSP1 0 0 C 1st Edition May 31 2000 00 8 Press the or key to display the required setpoint The figure below shows an example of the parameter set to 25 0 C S...

Страница 42: ...t to 20 min 0h20 SET ENT PT No RUN RESET DISP MODE changing MENU PROG PRG 26 segment time TIME 0h20 16 Press the SET ENT key once to register the setpoint SET ENT PT No RUN RESET DISP MODE MENU PROG P...

Страница 43: ...key once to register the setpoint SET ENT PT No RUN RESET DISP MODE MENU PROG PRG 31 PV event 1 set point PE1 5 0 C 26 Press the SET ENT key once to display the Event Number parameter EV2 SET ENT PT N...

Страница 44: ...t The figure below shows an example of the parameter set to time event 1 setpoint 1 SET ENT PT No RUN RESET DISP MODE changing MENU PROG PRG 29 event 1 no select EV1 1 34 Press the SET ENT key once to...

Страница 45: ...e Junction Code parameter JC for segment 2 The setpoint of this parameter is not changed in this example SET ENT PT No RUN RESET DISP MODE MENU PROG PRG 53 junction code select JC 0 43 Press the SET E...

Страница 46: ...OG PRG 26 segment time TIME 0h10 48 Press the SET ENT key once to register the setpoint SET ENT PT No RUN RESET DISP MODE MENU PROG PRG 26 segment time TIME 0h10 49 Programming is now complete Press t...

Страница 47: ...tarting target setpoint SSP1 After change Program operation begins with the current PV value The time setpoints of segment 1 precede others Before change The Target Setpoint TSP1 program parameter for...

Страница 48: ...ENT PT No RUN RESET DISP MODE MENU PROG PRG 5 start code select STC 0 8 Press the or key to display the required setpoint The figure below shows an example of the parameter set to time prioritized PV...

Страница 49: ...t two digits the segment number SET ENT PT No RUN RESET DISP MODE MENU PROG PRG 24 target set point 1 TSP1 80 0 C PV Display 12 Press the or key to display the required setpoint The figure below shows...

Страница 50: ...or key DISP key DISP DISP key SET ENT Event number On time of time event Off time of time event PV event type PV event setpoint Final target setpoint Time set segment time Ramp set segment time PID g...

Страница 51: ...attern Shows the number of remaining unused events Program pattern copying Program pattern clearance key or key key SET ENT key SET ENT key or key key or key key SET ENT key SET ENT DISP key These par...

Страница 52: ...4 Uses the 4th group of PID parameters 5 to 8 Likewise selecting these numbers uses the 5th to 8th groups of PID parameters Note For segment PID the controller uses the 1st group of PID for operation...

Страница 53: ...up Use the program pattern setup chart discussed in 3 2 Example of Program Pattern Setup Charts of this chapter to record your setpoints of program parameters Located in Main menu PROG Submenu PRG Par...

Страница 54: ...t times Same as the 1st group of wait times 4 WTM 4th group of wait zones Same as the 1st group of wait zones 4 WZ1 5th group of wait times Same as the 1st group of wait times 5 WTM 5th group of wait...

Страница 55: ...V high limit energized no stand by action 2 PV low limit energized no stand by action 3 Deviation high limit energized no stand by action 4 Deviation low limit energized no stand by action 5 Deviation...

Страница 56: ...Deviation low limit PV Target SP Deviation setpoint Open unlit Hysteresis Closed lit 4 De energized on PV high limit De energized on PV low limit PV Open lit Alarm setpoint Hysteresis Closed unlit 9...

Страница 57: ...w of Program Patterns and 3 2 Example of Program Pattern Setup Charts You can register as many as 300 program patterns with the UP750 controller Create as many copies of the chart as necessary First f...

Страница 58: ...PE3 off time of time event OFF3 Event number EV4 PV event type TY4 on time of time event ON4 PV event setpoint PE4 off time of time event OFF4 Event number EV5 PV event type TY5 on time of time event...

Страница 59: ...wait zones 4 WZ1 4th group of wait times 4 WTM 3rd group of wait zones 3 WZ1 3rd group of wait times 3 WTM 2nd group of wait zones 2 WZ1 2nd group of wait times 2 WTM 1st group of wait zones 1 WZ1 1st...

Страница 60: ...create programs according to the chosen options 1 Creating programs by setting final target setpoint and time unit As shown in the figure below this method creates programs by setting a segment time a...

Страница 61: ...preceding or the starting target setpoint if this is the point of starting program operation Segment time Define as hour and minute or minute and second For example configure segment 1 so the tempera...

Страница 62: ...2 Letting the controller start from the current setpoint and run according to time settings defined for segment 1 This method is not available if the SEG T Segment Setting Method parameter is set to...

Страница 63: ...e PID The UP750 offers two methods of PID switching One of the methods is to automatically switch between groups of PID constants according to the temperature zone The other method is to automatically...

Страница 64: ...group of PID constants 2nd group of PID constants 1st group of PID constants Maximum value of PV input range RH1 Minimum value of PV input range RL1 Segment 1 Segment 2 Reference point 2 2 RP1 Refere...

Страница 65: ...int Segment 1 Segment 2 PV input value Reference deviation RDV1 1 2 2 1 1 2 Method 2 As shown in the figure below the controller selects an appropriate group of PID constants for each zone and if the...

Страница 66: ...the seg ment in question to 1 Time Setpoint End of program Suspending the Progress of a Program Wait Function When a running program moves from one segment to another the wait function places the prog...

Страница 67: ...r of segments included in the selected program pattern the remaining time of the segment for which operation is in progress the current number of repetitions RCY and the total sum of repetitions Targe...

Страница 68: ...toring only Operating Displays for Single loop Heating Cooling Control Setpoint Display On the Setpoint display LCD the controller displays the current target setpoint SP the program pattern number PT...

Страница 69: ...the selected program pattern Event Display On the Setpoint display LCD the controller displays the event number for which an event has occurred For monitoring only However allows the setpoint and seg...

Страница 70: ...ontrol element results in inconvenience Processes where variations in PV may exceed an allowable range adversely affect ing product quality 1 Bring the operating display into view display appears at p...

Страница 71: ...ng auto tuning the panel indications become as shown below PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2 TME AL 1 1 2 3 4 MAN2 PRG RST HLD LOC MAN1 CAS SP 10 0 C PTNO 1 PID 1 SEGNO 1 3 OUT 100 0...

Страница 72: ...ey once to display the parameter 1 P SET ENT PT No RUN RESET DISP MODE MENU LP1 1 PID 1 proportional band 1 P 5 0 7 Press the or key to display the required setpoint SET ENT PT No RUN RESET DISP MODE...

Страница 73: ...rogram pattern number cannot be selected by key operation 1 Bring the operating display into view appears at power on PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2 TME AL 1 1 2 3 4 MAN2 PRG RST H...

Страница 74: ...starts PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2 TME AL 1 1 2 3 4 MAN2 PRG RST HLD LOC MAN1 CAS PTNO 1 SEGNO 1 3 RCY 0 0 SP 25 0 C TM 0h20 Start of operation Displays the time of segment 1 PR...

Страница 75: ...everal times to display the MODE MAN1 mode parameter To change from MAN to AUTO mode Press the MODE key several times to display the MODE AUTO1 mode parameter The figure below is an example of changin...

Страница 76: ...tween AUTO and MAN PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2 TME AL 1 1 2 3 4 MAN2 PRG RST HLD LOC MAN1 CAS SP 30 0 C PTNO 1 PID 1 SEGNO 1 3 OUT 30 0 MAN1 lamp ON 2 Press the or key to change...

Страница 77: ...he key held down longer you enter the state of manipulating the heating side output and its value begins to increase Cooling side manipulated output Heating side manipulated output Output DB 12 4 Dead...

Страница 78: ...ion Press the MODE key once to display the HOLD OFF mode parameter The figure below is an example of enabling the hold mode of program operation PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2 TME...

Страница 79: ...2 TME AL 1 1 2 3 4 MAN2 PRG RST HLD LOC MAN1 CAS PTNO 1 SEGNO 2 3 RCY 0 0 SP 80 0 C TM 0h20 This symbol appears for soak segments only HLD lamp ON 2 Press the SET ENT key once to display the symbol PV...

Страница 80: ...Y 0 0 SP 30 0 C TM 0h17 Indicates the controller is running on segment 1 PRG lamp ON 2 Press the MODE key twice to display the ADV ON mode parameter PV SET ENT PT No RUN RESET DISP MODE PVE2 PVE1 PV2...

Страница 81: ...0 0 SP 40 0 C TM 0h14 Indicates the controller is running on segment 1 PRG or RST lamp ON 2 Press the MODE key several times to display the LOC ON mode parameter PV SET ENT PT No RUN RESET DISP MODE...

Страница 82: ...HLD LOC MAN1 CAS PTNO 1 SEGNO 0 3 RCY 0 0 SP 50 0 C TM L The symbol L represents a local setpoint LOC lamp ON 2 Press the or key to change the local setpoint PV SET ENT PT No RUN RESET DISP MODE PVE2...

Страница 83: ...g Is display faulty Yes No Turn off power and then turn it on again Is I O signal faulty Yes No Check the instrument s I O specifications Check the supply voltage Check the specifications of I O count...

Страница 84: ...tion below Parameter error Normal action 0 or less or OFF Normal action Normal action E000 E001 E002 Stopped Display position Note 1 2 Note 1 PV display 2 Setpoint display An error code is displayed i...

Страница 85: ...al action Stopped Normal action Normal action Normal action Normal action Decimal point at right end lights Runaway due to defective power or noise Undefined Faulty if power off on does not reset star...

Страница 86: ...his refer to 2 Initial Settings With the parameters RH1 RL1 SDP1 SH1 and SL1 it is possible to scale the input signal and change its number of decimal places Also check that these param eters are conf...

Страница 87: ...oth NOTE Do not use alcohol benzine or any other solvents 5 2 2 Replacing Brackets When the brackets are broken or lost purchase the following brackets for replacement Target Model Part No UP750 T9115...

Страница 88: ...ot conducting any electricity 1 Before attaching the terminal cover fold it once or twice so that the side which has the Handle With Care symbol is on the outside Fold over Grooved Fold over Alert sym...

Страница 89: ...thium battery for backup About 10 years rated About 10 years rated Service life Alarm output relays About 100 000 more ON OFF operations or with resistance load Control output relays About 100 000 mor...

Страница 90: ...t for any other purpose other than to replace the control output relays 1 Insert a flat blade screwdriver tip width of 6 mm is recommended into the opening with the tip in parallel with the front pane...

Страница 91: ...RJC sensor 5 The location and number of the relays differ depending on the model code of the UP750 Confirm the location of the control output relay to be replaced before pulling out the relay Relay UP...

Страница 92: ...ply power to the controller and confirm that the initial operating display is shown If the operating display is not shown properly turn off the controller and pull out the internal unit Then insert it...

Страница 93: ...ating Parameter Map and Setup Parameter Map for UP750 as a guideline for setting parameters These maps are helpful in finding the positions of the displays when setting the param eters and should be u...

Страница 94: ...SET PAR HOLD LOC SST ADV MODE A M2 MODE A M1 MODE LSP CAS or DISP DISP SET1S DISP DISP MODE SET3S 1 Not displayed for ON OFF control 2 Not displayed for heating cooling control 3 Displayed for heatin...

Страница 95: ...splayed when UP mode is Cascade control Loop control with PV switching Dual loop control Temperature and humidity control Cascade control with two universal inputs Loop control with PV switching and t...

Страница 96: ...BS1 SET AIN OK A LC3 A SR3 A FL3 A BS3 TRND TSC1 TSC2 TTM SET DISP A LC2 A SR2 A FL2 A BS2 UP750 Setup Parameter Map Main menu submenu To operating parameter setting display main menu PROG on the prev...

Страница 97: ...R154 R155 R156 R157 R158 R251 R252 R253 R254 R255 R256 R257 R258 PTN 7 PTN 6 PTN 5 PTN 8 DP1 DP2 RL2 RH2 UNI2 IN2 RJC2 BSL2 SL2 SH2 SDP2 P RL1 P RL2 P RH2 P DP2 P UN2 Note The parameter items shown on...

Страница 98: ...n the communication func tion is used ex AUTO1 0 MAN1 1 Operation Mode Parameters Located in MODE key MODE key on the instrument s front panel Parameter Symbol Name of Parameter Setting Range and Desc...

Страница 99: ...F 0 1 to 120 sec Used when the PV input value fluctuates OFF 0 PV input bias 100 0 to 100 0 of PV input range span Used to correct the PV input value 0 0 of PV input range span 1 0 of PV input range s...

Страница 100: ...ON OFF action Program setpoint Hysteresis PV value Output On Off Deviation PV SP Direct action Reverse action Control output 0 100 ON OFF control hysteresis Heating side ON OFF control hysteresis in...

Страница 101: ...If you are using two or more groups of PID parameters use the following table to record their values Parameter n P n I n D n OH n OL n MR n H n DR n Pc n Ic n Dc n Hc n DB n PO n Oc n 2 n 3 n 4 n 5 n...

Страница 102: ...1 a8 1 b3 1 b4 1 b5 1 b6 66 7 to 105 0 of PV input range 66 7 to 105 0 of PV input range span Ten segment linearizer output Ten segment linearizer approximation 66 7 to 105 0 of PV input range 66 7 t...

Страница 103: ...ent linearizer approximation Ten segment linearizer 1 input 7 66 7 to 105 0 of PV input range 0 0 of PV input range Ten segment linearizer 1 output 7 66 7 to 105 0 of PV input range span 66 7 to 105 0...

Страница 104: ...ation OFF 0 Not cleared ON 1 Cleared OFF 0 Program setpoint 1 limiter upper limit Program setpoint 1 limiter lower limit Program setpoint 2 limiter upper limit Program setpoint 2 limiter lower limit 1...

Страница 105: ...Allows margins to be set for a PV event setpoint With the hysteresis settings it is possible to prevent relays from chattering 0 Allows the instrument alarm function to be enabled or disabled accordin...

Страница 106: ...t Open unlit Closed lit 8 18 Deviation low limit Target SP PV PV Deviation setpoint Open unlit Hysteresis Closed lit 4 14 De energized on PV high limit De energized on PV low limit PV Open lit Alarm s...

Страница 107: ...ilure and starts computation from the preset output value CONT 0 R MD PID group number Allows you to determine how many groups of setpoint alarm and PID parameters the controller should show 1 Show on...

Страница 108: ...Setting Target Item in CD ROM RH1 RL1 Analog Input Computation Parameters Located in Main menu CMLP Submenu AIN Parameter Symbol Name of Parameter Setting Range and Description Initial Value User Set...

Страница 109: ...lable when the type of control output is not current or voltage pulse The output is provided via terminals 16 and 17 OFF 0 Disable 1 PV1 2 SP1 3 OUT1 4 LPS loop power supply 15 V 5 PV2 6 SP2 7 OUT2 Se...

Страница 110: ...main menu PROG display OFF 0 Unlock ON 1 Lock OFF 0 PROG Locking of front panel MODE key OFF 0 Unlock ON 1 Lock OFF 0 MODE Parameter Symbol Name of Parameter Setting Range and Description Initial Val...

Страница 111: ...registration R256 Output flag registration R257 Output flag registration R258 DO3 DO4 DO5 DO6 DO7 5129 5130 5131 5133 Open collector transistor output flag registration for DO4 Open collector transis...

Страница 112: ...LOC HOLD ADV PTN 2 PTN 3 PTN 4 Bit 4 of program pattern number 0 MG1 MG2 MG3 MG4 Interruptive message display 1 0 Interruptive message display 2 0 Interruptive message display 3 0 Interruptive messag...

Страница 113: ...on the PV input type Depends on the PV input type RL1 Max value of PV input scale shown when in voltage input mode Set the read out scale of voltage mode PV input 19999 to 30000 where SL1 SH1 SDP1 SH...

Страница 114: ...ingle loop control it is shown on the display Although not used in single loop control it is shown on the display Although not used in single loop control it is shown on the display Although not used...

Страница 115: ...and 100 output levels at which the values are presented via OUTPUT 3 terminals and See Performing Split Computations below 5 0 to 105 0 0 0 100 0 0 0 100 0 0 0 Set the values of segmental points for t...

Страница 116: ...nalog Output 3 100 Segmental Point A3H parameter to 0 6 Set the Analog Output 3 0 Segmental Point A3L parameter to 75 The figure below shows an example where both analog outputs 1 and 3 are set to the...

Страница 117: ...tput 3 100 Segmental Point A3H parameter to 75 6 Set the Analog Output 3 0 Segmental Point A3L parameter to 0 The figure below shows an example where both analog outputs 1 and 3 are set to the current...

Страница 118: ...e maximum number of stations connectable is 31 1 ADR1 Protocol selection 2 0 PSL2 Minimum response time 2 0 to 10 10 ms 0 RP T2 Baud rate 2 600 0 1200 1 2400 2 4800 3 9600 4 19200 5 38400 6 bps 9600 4...

Страница 119: ...50 to 100 Heating side output limiter PV SP Manual MV output Communication Heating cooling control provides two methods in which either none of the heating and cooling side outputs are presented or b...

Страница 120: ...Blank Page...

Страница 121: ...7 Function Block Diagram and Descriptions This chapter contains the function block diagrams for Single loop control Single loop heating cooling control For details on these function block diagrams re...

Страница 122: ...operation Preset output 17 16 Current or pulse terminals and Relay terminals and 2 3 1 Current terminals and 15 14 Current terminals and 17 16 Terminal Parameter Function Analog signal Contact signal...

Страница 123: ...o 103 R251 to 258 R151 to 158 Analog input range conversion Analog input bias Square root extraction Analog input filter 10 seg linearizer approx bias PV input bias PV input filter Input selection Uni...

Страница 124: ...ction can be set by the following parameters Setup Parameters Function Parameter Input selection IN1 Unit selection UNI1 Analog input range conversion RH1 RL1 SDP1 SH1 SL1 UPMD UPMD UPMD IN IN IN Anal...

Страница 125: ...N For example set contact input 2 DI2 only to ON to change the program pattern 1 to the program pattern 2 Set contact input 1 DI1 and contact input 2 DI2 to ON to select the program pattern 3 Switchin...

Страница 126: ...time CT1 Cooling side control output cycle time CTc1 UPMD UPMD UPMD OUT OUT OUT Analog output 1 type AO1 UPMD OUT Analog output 2 type cooling side AO2 UPMD OUT Main menu Submenu Operating Parameters...

Страница 127: ...L1 Retransmission output 2 type RET2 CMLP CMLP CMLP RET RET RET Retransmission output 2 scale RTH2 RTL2 CMLP RET Main menu Submenu 15 V DC Loop Power Supply The 15 V DC loop power supply OUTPUT3 uses...

Страница 128: ...Blank Page...

Страница 129: ...al for Single loop Control Manual No IM 05E01B02 41E May 2000 1st Edition Newly published Written by Products Documents Controllers Conditioners Division Yokogawa M C Corporation Published by Yokogawa...

Страница 130: ...Blank Page...

Отзывы: