Suppressing Integral Action (Anti-reset Wind-up)
Description
Where there is a large deviation at the start of the control operation, for example, integral
outputs are accumulated and the PV exceeds the SP, thereby causing the output to
overshoot. To avoid this, the controller provides an anti-reset wind-up function for
suppressing an extreme integral output by stopping PID computations. Same applies to
the case of undershoot.
100
OH
0
PID computations stop
SP
PID computations restart
OH: Output high limit
Time
Output (%)
Time
PV
Deviation band (AR):
the ratio of (PV
–SP) to
proportional band
PV
The parameter AR sets the point (by deviation band (%)) to restart the PID computation
that is suspended by the controller’s anti-reset windup function. PID computation restarts
when the deviation band has decreased to the AR setpoint. When the parameter AR is
set to AUTO, the controller automatically determines the point at which to restart the PID
computation.
Deviation band (= Setpoint of AR) =
× 100 (%)
Proportional band
|
PV
–
SP
|
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
AR
Anti-reset windup
STD
AUTO, 50.0 to 200.0%
TUNE