<2. INSTALLATION, PIPING, AND WIRING>
2-7
IM 12B01B30-02EN 2nd Edition : June 09 , 2021-00
Table2.1
Specification of power cable
Rated voltage
300V or above
Rated temperature
75°C or above
Number of cores, Wire diameter 3
L, N, G: 0.75 to 2.5 mm
2
(AWG18 to14)
Sheath outer diameter
Ø6.5 to Ø12.5 mm
Cable termination
Strip the outer sheath of 80 mm, provide the termination.
L, N: M3 round terminal
G: M4 round terminal
Connect the power supply cable to the terminal. Refer to Figure 2.8.
This instrument does not have a power supply switch. The power supply line must be equipped
with a double switch. Grounding wiring connected to the smart unit shall satisfy Class D
(grounding resistance: 100 Ω or less). Fasten the M3 screw (L, N) with the tightening torque of
0.6 N·m, M4 screw (G) with 1.4 N·m. (Figure 2.8)
2.1.4
Wiring with PG400
When the suffix code -U1 (Ultrasonic cleaning) is specified, PG400 Pulse Generator for Clean
Unit is supplied with the product.
For PG400, read PG400 User's Manual IM 19C01B05-01EN.
Provide wiring of Oscillator cable and Power cable for PG400, by referring to Figure 2.1 or Figure
2.2-Figure 2.3.
Connect the Cable for PG400 to Detection unit, not to Smart unit of TB820D.
Connect the connector as shown on the left in Figure 2.5 and thread it through the clamp as
shown on the right. Make sure that the connector part is above the clamp. Run the cable along
the side of the housing and lay it in the back.
clamp
Figure 2.5
Cable for PG400
2.1.5
When Relay box for solenoid valve is included
When the suffix code -A5 (Relay box for solenoid valve) is specified, a Relay Box is included as
shown in the Figure 2.2. Wire the cables of Power cable for Smart unit (D), Cable for Relay box
control (E), and Cable for SV (F).
Ground Terminal
101
102
201
202
301
302
Power supply cable (C)
Cable for SV (F)
Power cable for FLXA402T (B)
View from the bottom
Cable for SV control (E)
Power cable for Smart unit (D)
SV3 cable
SV2 cable
SV1 cable
SV4 cable
Figure 2.6
Wiring Relay Box