3-49
TI04L55B01-01EN
3.3.17
OPC-UA SERVER (/E3)
Data acquired by the GM can be accessed through Ethernet communication from a host system
(OPCUA client).
Equipped with an OPC-UA server function. GM measurement data can be retrieved directly from
a host system, such as SCADA and MES.
GM
Ethernet
OPC-UA server
OPC-UA client
Production site
Temperature
Pressure
Flow rate
Read
Write
Voltage
Others
I/O channel
Math channel
Communication channel
Device information
l
Specifications
Classification
Function
Communication
Type
OPC-UA Server
Encoding
UA Binary
Protocol
OPC UA TCP
Maximum number
of connections
3 sessions
Profile
Micro Embedded Device Server
Language
English
Security
Type
None
Encryption
None
Login
Anonymous, Username
Data acquisition
Measurement channel,Computation channel, Communication
channel value and alarm status
Data writing
Measurement channel (DO channel only),
Communication channel
Other acquired information
Device name, serial,number, time, device status
Number of items
300 max. (MonitoredItem/Session)
Fastest period
100ms
Service set
Discovery
FindServers,
GetEndpoints
SecureChannel
OpenSecureChannel,
CloseSecureChannel
Session
CreateSession,
ActivateSession,
CloseSession
View
Browse,
BrowseNext,
TranslateBrowsePathsToNodeIds