<APPENDIX 1. LIST OF PARAMETERS FOR EACH BLOCK OF RAMC>
A-1
All Rights Reserved. Copyright © 2006, Rota Yokogawa
IM 01R01B02-01E-E 5th edition October 01, 2020 -00
Appendix 1. List of Parameters for each
Block of RAMC
NOTE
• With Factory Reset (setting: 1) the parameters OUT_SCALE and PV_SCALE must be reconfigured.
• When changing flow units, the parameter PV_SCALE must be reconfigured.
• Changes to the process variables between mass- and volume flow also require
a change of the parameter
CHANNEL in the AI block to make this change available in the OUT parameter.
• To avoid unusable alarm status information, the upper alarm/warning limits must always be above the lower
alarm/warning limit.
Legend:
• "-": not defined
•
"n.a.": not applicable
•
R: Read
•
W: Write
A1.1 Physical Block
Block name
Physical Block
Slot
0
Abs.
Index
Parameter
Sub-
Parameter
Label
Data Type/
Structure
Read/
Write
Initial value
Functional Description
16
BLOCK_OBJECT
-
DS-32
R/-
-
Indicates the following block
characteristics
Reserved
-
Unsigned8
R/-
250: Not used
For future use (not available)
Block_Object
Block Object
Unsigned8
R/-
0x01: Physical Block
Kind of block
Parent_Class
Parent Class
Unsigned8
R/-
0x01: Transmitter
Superior device classification
Class
Class
Unsigned8
R/-
0x06: Variable Area
Flow Meter
Device classification
Dev_Rev
Device Revision
Unsigned16
R/-
1
Assigned device driver versions
(e.g. EDD)
Dev_Rev_Comp
Device Revision
Compatibility
Unsigned16
R/-
1
Lowest device revision supported by
the device
DD_Revision
-
Unsigned16
R/-
1
For future use (not available)
Profile
Profile
OctetString
R/-
0x40: PROFIBUS PA
Profile for Process
Control Devices,
0x02: Compact
Class B
Used Profile
Profile_Revision
Profile Revision
Unsigned16
R/-
0x0302: Version 3.02 Used Profile version
Execution_Time
-
Unsigned8
R/-
0
For future use (not available)
Number_of_
Parameters
No. of Parameters
Unsigned16
R/-
39
Number of used parameters
Address_of_
View_1
-
Unsigned16
R/-
0x00E6: slot 0, index
230
Reference to View_1 parameter
Number_of_Views -
Unsigned8
R/-
2
Number of Views available
17
ST_REV
Static Revision No. Unsigned16
R/-
0
Indicates the revision level of the
described block. Increments each
time a static parameter (S) changes
18
TAG_DESC
TAG
OctetString
R/W
RAMC-PA_P or det.
by ordered scale
Block specific TAG for customer use
19
STRATEGY
Strategy
Unsigned16
R/W
0
User-specified value e.g. for configu
-
ration or diagnostics as a sorting key