<5. Maintenance>
5-1
IM 02M04B01-01EN
5. Maintenance
5.1 Basic Troubleshooting
DIFFICULTY: No reading (or very low reading) at
output gauge.
F0501.ai
1
2
Output gauge
4
1. Check that 140 kPa (1.4 kgf/cm
2
) is supplied to
controller.
2. Check for measurement reading.
3. Clean restrictor. (refer to section 5.3).
4. Disconnect output line and plug controller
output with finger.
5. Adjust set point knob (or remote set point, if
present) so that set point index goes above and
below measurement pointer. If output gauge
indicates normal control action, there is a leak
in output line or control valve.
6. If output gauge still indicates no control action,
a. Check controller for damage or leaks.
b. Replace amplifier (refer to section 5.4).
c. Check control unit alignment (refer to section
5.11 and 5.12).
DIFFICULTY: Maximum pressure at all times at
output gauge.
1. Check for mechanical damage resulting in
nozzle always being covered by flapper.
2. Check for misalignment of amplifier gasket,
resulting in plugging.
3. Replace pneumatic amplifier (refer to section
5.4).
4. Clean nozzle (refer to section 5.3).
5. Check control unit alignment (refer to section
5.11 and 5.12).
5.2 Identification of Major
Components in Controller
(1) Model MC43-
N-N
F0502.ai
Measurement
pointer
Set point index
Set point and
measurement dial
Output gauge
Measurement
element
(pressure type
illustrated)
Reset
assembly
(optional)
Derivative
assembly
(optional)
Control unit
Set point knob
Controller without
automatic-manual
transfer system
Pneumatic
amplifier
(2) Model MC43-
C-P
F0503.ai
Remote set point element
(optional)
Pneumatic amplifier
Auto-man transfer system
(optional)
Shutoff for air to automatic
control section
(controller with automatic-manual
transfer system).
Содержание MC43
Страница 1: ...User s Manual MC43 Pneumatic Indicating Controller IM 02M04B01 01EN IM 02M04B01 01EN 13th Edition...
Страница 34: ...2 CMPL 02M04B01 01E Feb 2012 Subject to change without notice...
Страница 36: ...4 CMPL 02M04B01 01E Jan 2003 Subject to change without notice...
Страница 38: ...6 CMPL 02M04B01 01E Jan 2003 Subject to change without notice...