Thank you for purchasing the JUXTA Signal Conditioner.

Please read through this manual before use for correct handling.

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

Phone: +81-422-52-7179  Facsimile: +81-422-52-6793

http://www.yokogawa.com/ns/juxta/im/

You can download the latest manuals from the following website:

IM 77J01Q08-01E

7th Edition Aug. 2020(YK)

CAUTIONARY NOTES FOR SAFE USE OF THE 

PRODUCT

This User’s Manual should be carefully read before installing and 

operating the product. Please keep this User’s Manual for future 

reference.

Doc. Name

Doc. Number 

Model VJQ8 Pulse to Analog Converter (User’s Manual) IM 77J01Q08-01E

(This manual)

Model VJQ8 Pulse to Analog Converter (General 

Specifications)

GS 77J01Q08-01E

User’s manuals in the above table are essential parts of the 

product; keep it in a safe place for future reference.

This manual is intended for the following personnel;   

 • Engineers responsible for installation, wiring, and maintenance 

of the equipment.

 • Personnel responsible for normal daily operation of the 

equipment.

The following symbol is used on the product and in this manual to 

ensure safe usage.

 WARNING

Calls attention to actions or conditions that could 

cause serious or fatal injury to the user, and indicates 

precautions that should be taken to prevent such 

occurrences.

 CAUTION

Calls attention to actions or conditions that could 

cause injury to the user or damage to the instrument 

or property and indicates precautions that should be 

taken to prevent such occurrences.

CHECKCHECKING PRODUCT SPECIFICA-

TIONS AND PACKAGE

(1) 

Checking the Model and Product Specifications

Check that the model and specifications indicated on the 

nameplate attached to the main unit are as ordered.

(2)  Packaged Items

Check that the package contains the following items:

 • VJQ8: 1 unit

 • Tag number label: 1 sheet

 • Range label: 1 sheet

 •

Shunt resistor (when optional code “/R□” is specified): 1

 • User's Manual (this manual): 1 copy

GENERAL

This plug-in type pulse to analog converter receives contact 

pulse, voltage pulse, or current pulse from the field and converts 

the signal into isolated DC current or voltage signals.

 • Output-2 can be selected from DC voltage signal, DC current 

signal, communication function (RS-485), or alarm output (2 

relay contacts).

 • Various parameters such as input range can be set and 

modified using a PC (VJ77(sold separately)) or Handy 

Terminal (JHT200(sold separately)) and the like.

MODEL AND SUFFIX CODES

Model

Suffix codes

Description

VJQ8

-0

□ □ -□ □ □

0

/□

Pulse to Analog Converter 

(Multi-function)

-0

Always 0

Output

configuration

1

1 output

2

2 outputs

Power supply

6

100-240 V AC/DC 

(*1)

7

15-30V DC 

(*2)

Transmitter Power 

Supply

-1

12V DC±10%

-2

24V DC±10%

Output-1

A

4 to 20mA DC

B

2 to 10mA DC

C

1 to 5mA DC

D

0 to 20mA DC

E

0 to 16mA DC

F

0 to 10mA DC

G

0 to 1mA DC

1

0 to 10mV DC

2

0 to 100mV DC

3

0 to 1V DC

4

0 to 10V DC

5

0 to 5V DC

6

1 to 5 V DC

7

−10 to +10V DC

Z

(Custom Order)

(*3)

Output-2

A

4 to 20mA DC

6

1 to 5V DC

P

Communication function 

(RS-485)

T

Alarm output 

(2 relay contacts)

N

None

0

Always 0

Options

Blank: With socket

/SN

Without socket

/R100

With 100 Ω shunt resistor 

(*4)

/R220

With 220 Ω shunt resistor 

(*4)

/R510

With 510 Ω shunt resistor 

(*4)

/R1000

With 1000 Ω shunt resistor 

(*4)

/R2200

With 2200 Ω shunt resistor 

(*4)

*1 Operating range: 85-264 V

*2 Operating range: 12-36 V

*3 DC voltage signal or DC current signal

*4 Specify when current pulse input

Model VJQ8

Pulse to Analog Converter 

(Multi-function)

(Isolated Single-output and Isolated Dual-

output Types)