Analog Positioner

1. CAUTIONARY NOTES FOR SAFE USE OF THE PRODUCT

This User’s Manual should be carefully read before installing and oper-
ating the product.  The following symbol is used on the product and in
this manual to ensure safe use.

This symbol is displayed on the product when it is
necessary to refer to the User’s Manual for information on
personnel and instrument safety.  This symbol is displayed
in the User’s Manual to indicate precautions for avoiding
danger to the operator, such as an electric shock.

The following symbols are used only in this manual.

IMPORTANT

Indicates that operating the hardware or software in a
particular manner may cause damage or result in a system
failure.

NOTE

Draws attention to essential information for understanding
the operations and/or functions of the product.

2. CHECKING PRODUCT SPECIFICATIONS AND PACKAGED ITEMS

(1) Checking the Model and Product Specifications

Check that the model and specifications indicated on the nameplate
attached to the side face of the main unit  are as ordered.

(2) Packaged Items

Check that the packing carton contains the following items:

UZ011: 1

Spacer (used for DIN rail mounting): 1

External resistor, 1 (Shunt resistor used when 4 to 20mA DC input)

User’s Manual (this manual: IM 77J04A01-01E): 1 copy

3. GENERAL

This UZ011 is a plug-in type Analog Positioner.

Internal timer prevent frequent ON-OFF of motor valve.

Retransmission output can be used to monitor the motor position value.

Feedback slide resistance : 100 

 to 10 k

Easy adjustment operation, 

1% Setting Accuracy.

4. MOUNTING METHOD

NOTE

Insert/pull out the main unit into/from the socket vertically
to the face of socket.  Otherwise the terminals are bent and
it may cause a bad contact.

IM UZ011-01E

1st Edition  Aug. 2000 (MC)

2nd Edition June 2004 (YK)

4.1

Wall Mounting

Remove the stoppers (top and bottom) from the product and pull out
the main unit from the socket.  Fix the socket on the wall using two M4
screws.  Next, insert the main unit into the socket and fasten the main
unit with the stoppers (top and bottom).

5 or more

(51)

(85)

Socket

Socket

Stopper

Main unit

Mounting

screws

<Mounting Dimensions>

Unit: mm

40

±

0.2

Pitch: 55 or more

 2-ø4.5 or 2-M4

Note:
(1) More than 5 mm interval is 

required for side-by-side 
close mounting.

(2) Use the supplied spacer for 

DIN rail mounting to keep 5 
mm interval.

4.2

DIN Rail Mounting

Insert a DIN rail into the upper part of the DIN rail groove on the rear of
the socket, and then slide the slide lock at the lower part of the socket
upwards until the socket is fixed into position as shown below.

Slide lock

Spacer

DIN rail

DIN rail

Fit into here

Push

(Rear of the socket)

4.3

Using a Duct

When using a wiring duct, install the duct at leaset 20 mm away from
the top and bottom faces of the main unit.