IM 11G06A01-02EN
3-10
3. INSTALLATION
1st Edition : Oct. 27, 2023-00
l
Wiring power supply
Connect the specified power supply to the power terminal and connect a ground wire to the
ground terminal (P). The grounding should be D-class grounding. Use crimp terminals (for M4)
for the wires to be connected to the terminals. The tightening torque is 1.2 N•m. Applicable wire
diameters for power supply wiring lines are as follow.
IR800G: unrestricted
IR810G:
Ø
6.5 to
Ø
12 mm
L
N
N
L
IR800G
IR810G
earth
100 to 240V AC
100 to 240V AC
Ferrite core
(accessory)
Figure 3.5
Wiring power supply
CAUTION
M4 screw terminals should always be covered with a terminal block protective cover after wiring
for safety.
Thread the power cable
through the cable clamp
for installation.
Insert the supplied strapping band into the hole
and tie it to the power cable to secure it in place.
hole
strapping band (included)
ferrite core (included)
Figure 3.6
IR810G power cable installation