<13. General Specifications>
13-1
IM 01S01C01-01EN
13. General Specifications
13.1 Functional Specifications
Functional specifications for Fieldbus
communication conform to the standard
specifications (H1) of F
OUNDATION
fieldbus.
Supply Voltage
9 to 32 V DC for general use, flame proof type,
Type n, or nonincendive.
9 to 24 V DC for intrinsically safe type Entity model
9 to 17.5 V DC for intrinsically safe type FISCO
model
Communication Requirements
Supply Voltage: 9 to 32 V DC
Current consumption:
Steady condition: 15 mA (max)
Software download condition: 24 mA (max)
Ambient Temperature Limits
-20 to 70°C (-4 to 158°F)
Ambient Humidity Limits
0 to 100 %RH
LCD Display
84 column x 32 lines full-dot matrix with LED
backlight.
3 lines indication as
• Top line
14 alphanumerics indication of main description
(Main Tag) such as PD TAG of field device.
Scroll up to maximum 32 alphanumerics
• Middle line
5 digits process value inc/- sign and unit
of 5digits x 2 lines
• Bottom line
14 alphanumerics of communication status and
indicate description (Sub Tag) such as block
information.
Bar graph, Scroll bar, Page information, Scroll
direction information, Squawk
Process value
(Middle line)
Top line
Unit
(Middle line)
Bottom line
14 characters
14 characters
5 digits
5 digits
5 digits
F1301.ai
Display Scroll Functions
Single scroll and cyclic scroll (Scan mode)
Display up to 16 variables
EMC Conformity Standard:
EN 61326-1 Class A, Table 2
EN 61326-2-3
EN 61326-2-5 (for fieldbus)
Link Master Function:
Link Master function is supported.
Function Block:
Block name
Number
Execution time
Note
MAO
2
30 ms
Output eight analog signals from field deveces
IS
2
30 ms
Input Selector block provides selection of up to eight inputsand generate
an output based on the configured action
AR
2
30 ms
Arithmetic block permits simple use of popular measurement math func-
tion
PID
2
45 ms
Works as a field controller in conjunction with another function block.
SC
1
30 ms
An output of Signal Characterizer block is a nonlinear function of the
respective input. The function is determined by a table
IT
1
30 ms
Integrator block integrates a variable as a function of the time or accumu-
lates the counts
Содержание FVX110
Страница 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Страница 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Страница 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Страница 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Страница 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Страница 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...
Страница 20: ... 2 Handling Cautions 2 9 IM 01S01C01 01EN ...