6.6.2 Trend Object
It is possible to set the parameter so that the
function block automatically transmits Trend.
FVX110 has seven Trend objects, six of which are
used for Trend in analog mode parameters and
one is used for Trend in discrete mode parameter.
A single Trend object specifies the trend of one
parameter.
Each Trend object has the parameters listed in
Table 6.8. The first four parameters are the items
to be set. Before writing to a Trend object, it is
necessary to release the WRITE_LOCK parameter.
Table 6.7
Parameters for Trend Objects
Sub-
index
Parameter
Description
1
Block Index
Sets the leading index
of the function block that
takes a trend.
2
Parameter Relative
Index
Sets the index of
parameters taking a trend
by a value relative to the
beginning of the function
block.
3
Sample Type
Specifies how trends are
taken. Choose one of the
following 2 types:
1: Sampled upon
execution of a function
block.
2: The average value is
sampled.
4
Sample Interval
Specifies sampling
intervals in units of 1/32
ms. Set the integer
multiple of the function
block execution cycle.
5
Last Update
The last sampling time.
6 to
21
List of Status
Status part of a sampled
parameter.
21 to
37
List of Samples
Data part of a sampled
parameter.
Seven trend objects are factory-set as shown Table
6.8.
Table 6.8
Trend Object are Factory-Set
Index
Parameters
Factory Settings
32000 to
32005
TREND_FLT.1 to
TREND_FLT.5
Not used.
32006 TREND_DIS.1
Not used.
6.6.3 View Object
This object forms a group of parameters in a
block. One advantage brought by forming groups
of parameters is the reduction of load for data
transactions. View Object has the parameters listed
in Table 6.10 and 6.11. Purpose of View Objects is
shown in Table 6.9.
Table 6.9
Purpose of Each View Object
Description
VIEW_1 Set of dynamic parameters required by
operator for plant operation. (PV, SP, OUT,
Mode etc.)
VIEW_2 Set of static parameters which need to be
shown to plant operator at once. (Range etc.)
VIEW_3 Set of all the dynamic parameters.
VIEW_4
Set of static parameters for configuration or
maintenance.
Содержание FVX110
Страница 1: ...User s Manual FVX110 Fieldbus Segment Indicator IM 01S01C01 01EN IM 01S01C01 01EN 4th Edition ...
Страница 15: ... 2 Handling Cautions 2 4 IM 01S01C01 01EN ...
Страница 16: ... 2 Handling Cautions 2 5 IM 01S01C01 01EN ...
Страница 17: ... 2 Handling Cautions 2 6 IM 01S01C01 01EN ...
Страница 18: ... 2 Handling Cautions 2 7 IM 01S01C01 01EN ...
Страница 19: ... 2 Handling Cautions 2 8 IM 01S01C01 01EN ...
Страница 20: ... 2 Handling Cautions 2 9 IM 01S01C01 01EN ...