A2-54
IM 34M06C11-01E
(17) F3YC08-0C/F3YC08-0N Relay Output Module
Item
Specifications
F3YC08-0C
F3YC08-0N
Output type
Relay contact
Number of points
8
Common line type
All points independent
8 points/common
Isolation method
Mechanical insulation
Withstanding voltage
1500V AC for one minute between the group of terminals for external connection
and the internal circuit
Rated load
voltage range
(
maximum load
voltage
)
DC
5-24V
(
125V
)
AC
100-240V
(
264V
)
Maximum load current
2A/point
(
resistive load
)
2A/point, 8A/common line
(
resistive load
)
Maximum switching
capacity
530VA/point, or 60W/point (for resistive load)
Minimum load
voltage/current
5V DC, 10mA
Response
time
OFF
→
ON
10ms max.
ON
→
OFF
10ms max.
ON voltage
───
Off-time leak current
───
Service
life
Mechanical
20 million operations or more
Electrical
100,000 operations or more
(
rated load
)
Surge protector
*1
None
Fuse
None
Dissipating current
205mA
(
5V DC
)
Output display
*2
LED
(
Lit when output is on
)
Output status when the
program stops
HOLD/RESET
*3
When a sequence CPU module is used:
Default: RESET; can be set globally on a module-by-module basis.
When a BASIC CPU module is used:
No setting function; the status is always HOLD.
External power supply
Not required
External connection
18-point terminal block with M3.5 screws 10-point terminal block with M3.5 screws
Weight
180g
160g
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is required on the load side. Connect a
surge protector or a diode across the load nearby so that the module output terminal voltage will not exceed the
specified operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*3:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
WARNING
Don’t connect DC load and AC load to single module together.
Don’t connect loads from different AC sources to single module together.
In case of using these loads at once, connect to different relay output modules
separately.
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...