Common Specifications
Item
Specifications
Environment
Surrounding air temperature range
Operating : 0 to 55°C
*1
Storage
:
-20°C to 75°C
Surrounding humidity range
Operating : 10 to 90% RH (non-condensing)
Storage
:
10 to 90% RH (non-condensing)
Surrounding atmosphere
Must be free of corrosive gases, flammable gases or heavy dust.
Grounding
AC Power supply module
:
Protective earth (Comply with the regulation of each country.)
DC Power supply module
:
Functional earth
Noise immunity
Tested using a noise simulator with a noise voltage of 1500 Vp-p, pulse width of 1µs, rise time of 1 ns,
and repetition frequency of 25 to 60Hz.
For CE Marking-compliant modules, compliant to EN61326-1, EN61326-2-3
*4
and EN61000-6-2
Vibration resistance
Tested in compliance with JIS C60068-2-6 under the following conditions:
- Frequency ranges:
10 to 57Hz with an amplitude of 0.075mm
57 to 150Hz with an acceleration of 9.8m/s
2
(1G)
- Direction and sweep cycles: 10 times each in the X, Y, and Z directions
Shock resistance
Tested in compliance with JIS C60068-2-27 under the following conditions:
- Direction and sweep cycles: 3 times each in the X, Y, and Z directions with an acceleration of 147m/s
2
(98m/s
2
with DIN-rail mounting)
St
ruct
ure &
Appeara
nce
Structure
Designed for mounting inside a panel enclosure
Altitude of installation
Max. of 2000m above sea level
Compliance
with safety and
EMC
standards
*2
UL
UL508 approved, File No.E188707
(Overvoltage Category
*5
: II, Pollution Degree
*6
: 2)
CE
EMC Directive
*3
EN 61326-1 Class A, Table 2
EN 61326-2-3
*4,
EN 55011 Class A, Group 1
EN 61000-6-2, EN 61000-3-2, EN 61000-3-3 compliance
Low Voltage
Directive
EN 61010-1, EN 61010-2-201 compliance (Overvoltage Category
*5
: II, Pollution Degree
*6
: 2)
EN 61010-2-030 compliance (Measurement Category O)
*7
RoHS Directive
EN 50581 compliance
RCM
EN 55011 Class A, Group 1 compliance
EN 61326-1 Class A, Table 2
KC
Korea Electromagnetic Conformity Standard compliance
Cooling method
Natural-air cooled
Mounting
Direct mounting with M4-size setscrews
*8
or DIN-rail mounting (except for F3BU16-0N module)
Finish color
Light cobalt blue, equivalent to Munsell 6.2PB 4.6/8.8;
Lampblack, equivalent to Munsell 0.8Y 2.5/0.4
External dimensions
See the dimensional figures in Section A2.10, “External Dimensions.”
*1:
Some FA-M3 modules may have a narrower surrounding temperature range than 0-55
C. A system incorporating such
modules must be used within the narrower surrounding temperature range for such modules.
*2:
For details on conforming modules, see Appendix A2, “Standard compliant products”.
*3:
This product is classified as Class A for use in industrial environments.If used in a residential environment, it may cause
electromagnetic interference (EMI). In such situations, it is the user's responsibility to adopt the necessary measures
against EMI.
*4:
EN61326-2-3 is applicable only to F3CU04-
□□
.
*5:
The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four
categories. Overvoltage Category II applies to systems with a rated voltage of 220/230/240 V and applies to electrical
appliances, portable devices, etc.
*6:
The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a
reduction of dielectric strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to
an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by
condensation is to be expected.
*7:
EN 61010-2-030 is applicable only to modules with analog input terminal.
Don’t use analog input terminals of the FA-M3 for measurement on Mains Circuit, since it has no measurement category.
*8:
For details on the number of mounting screws, see subsection A3.2.2.
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...