A2-67
IM 34M06C11-01E
(23) F3YD32-1H Transistor Output Module (for high speed output)
Item
Specifications
Item
Specifications
Output type
Transistor contact
(sink type)
Service
life
Mechanical
─
Electrical
─
Protection
circuitry
Short-circuit
Controlled short-circuit current
Number of points
32
Common line type
8 points/common
Overheat
Output shutdown
Isolation method
Photocoupler isolation
Surge protector
*1
Active clamp circuit
Withstanding voltage
1500V AC for one minute
between the group of
terminals for external
connection and the
internal circuit
Fuse
None
Dissipating current
165mA (5V DC)
Output display
*2
LED (Lit when output is on)
Output status when the
program stops
HOLD/RESET
*3
When a sequence CPU module is
used:
Default: RESET
Can be set globally on a module-by-
module basis
*4
Rated load
voltage
(operating load
voltage range)
DC
12-24V DC
(10.2-26.4V DC)
AC
─
Maximum load
current
0.1A/point,
0.5A/common line
When a BASIC CPU module is used:
No setting function
The status is always HOLD
Response
time
OFF
→
ON 0.1ms max.
ON
→
OFF 0.1ms max.
ON voltage
0.5V DC max.
External power supply
12-24V DC, 30mA
External connection
One 40-pin connector
Off-time leak current
0.1mA max.
Weight
110g
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is also required on the load side. Connect
a surge protector or a diode across the load nearby so that the module output terminal voltage will not exceed the
specified operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*3:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
*4:
When F3SP22, F3SP28, F3SP38, F3SP53, F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module is
used, this setting can be specified in 16-point units.
CAUTION
Ensure that the polarity of the external power supply is correct. Otherwise, a short-circuit
condition may damage an output element and cause smoldering and scattering of chips.
Beware that wrongly connecting a connector wired for F3XD32 or F3XD64 to the
module may disable the protectors and damage internal elements.
Note
Operation of the protection circuitry:
- If short-circuit occurs, the ON voltage increases and the short-circuit current is
limited within the range 1-3A.
- If the short-circuit condition is removed, normal operation resumes.
- If the short-circuit condition persists, the short-circuit current may cause the
temperature of the output element to reach approx. 160°C, triggering the overheat
protector to shut down the output.
- If the temperature of the overheated output element then drops by about 10°C,
normal operation resumes.
- The overheat protector will not be triggered if the module is operated normally within
its specifications with no short-circuit condition.
- Both the short-circuit protector and overheat protector are designed to control
outputs individually. Under some short-circuit conditions, however, the overheat
protector may shut down not only its associated output but also other outputs.
- Short-circuit and overheat protectors are designed to protect the output element
against short-term short-circuit. Never leave the module in prolonged short-circuit
condition. Otherwise, the module enclosure may deteriorate or the PCB may be
discolored.
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...