<8. Detailed Data Setting>
8-9
IM 11M12A01-04E
11th Edition : Jul. 19, 2017-00
(3) Although oxygen concentration measurement “C” has fallen lower than the hysteresis set
value, that measurement exceeds the hysteresis set value before the preset delayed time
has elapsed. So, the alarm is not canceled.
(4) Oxygen concentration measurement “D” has fallen below the hysteresis set value and the
preset delayed time during measurement has elapsed, so the alarm is canceled.
8.3.3
Alarm Setting
Set the alarm setpoints following Table 8.7 listing parameter codes.
Table 8.7
Parameter Codes for Alarms
Set item
Parameter code
Set value
Oxygen concentration high-high alarm setpoint
D01
0-100% O
2
Oxygen concentration high alarm setpoint
D02
0-100% O
2
Oxygen concentration low alarm setpoint
D03
0-100% O
2
Oxygen concentration low-low alarm setpoint
D04
0-100% O
2
Humidity high-high alarm setpoint
D05
0-100% H
2
O
Humidity high alarm setpoint
D06
0-100% H
2
O
Humidity low alarm setpoint
D07
0-100% H
2
O
Humidity low-low alarm setpoint
D08
0-100% H
2
O
Mixing ratio high-high alarm setpoint
D11
0-1 kg/kg
Mixing ratio high alarm setpoint
D12
0-1 kg/kg
Mixing ratio low alarm setpoint
D3
0-1 kg/kg
Mixing ratio low-low alarm setpoint
D14
0-1 kg/kg
Oxygen concentration alarm hysteresis
D30
0-9.9% O
2
Humidity alarm hysteresis
D31
0-9.9% H
2
O
Mixing ratio alarm hysteresis
D32
0-0.1 kg/kg
Delayed alarm action
D33
0-255 seconds
Oxygen concentration high-high alarm detection
D41
0 Not detected
1 Detected
Oxygen concentration high alarm detection
D42
0 Not detected
1 Detected
Oxygen concentration low alarm detection
D43
0 Not detected
1 Detected
Oxygen concentration low-low alarm detection
D44
0 Not detected
1 Detected
Humidity high-high alarm detection
D45
0 Not detected
1 Detected
Humidity high alarm detection
D46
0 Not detected
1 Detected
Humidity low alarm detection
D47
0 Not detected
1 Detected
Humidity low-low alarm detection
D48
0 Not detected
1 Detected
Mixing ratio high-high alarm detection
D51
0 Not detected
1 Detected
Mixing ratio high alarm detection
D52
0 Not detected
1 Detected
Mixing ratio low alarm detection
D53
0 Not detected
1 Detected
Mixing ratio low-low alarm detection
D54
0 Not detected
1 Detected