<8. Detailed Data Setting>
8-10
IM 11M12A01-02E 16th Edition : Mar. 19, 2020-00
8.4.2
Setting Procedure
To set the output contact, follow these steps.
(1) Press the [Setup] key in the Basic panel display to display the Execution/Setup display.
(2) Select “Commissioning” in the Execution/Setup display. The Commissioning (Setup) display
then appears.
(3) Select the “Contact setup” in the Commissioning (Setup) display. The Contact setup display
shown in Figure 8.6 then appears.
(4) Select the desired output contact. This section shows an example where “Output contact1”
is selected (see Figure 8.7).
(5) Each set item and the selected items are briefly described in Table 8.6. The following
describes an example of setting where Output contact 1 is closed during calibration.
(6) Select “Others” in the Output contact 1 display. The “Contact1 Others” display shown in
Figure 8.8 then appears. Select “Calibration” in the Contact1 Others display.
(7) The ON or OFF selection display then appears. Select “ON” herein.
(8) Press the [Reject] key to go back to the previous display.
(9) Move the pointer to “During power-off the contact is open and in condition it is Open” and
press the [Enter] key. The “OFF” or “ON” selection display then appears. If you select “OFF,”
this means “Open” in normal conditions and “Closed” when the contact output is on.
CAUTION
The contact output 4 is fixed as “ close in power ON”, which cannot be changed by setting.
Output contact 1
Output contact 2
Output contact 3
lnput contacts
Enter
Contact setup
F8.7E.ai
Enter
Alarms
Others
During power-off the
contact is open and
in condition it is Open
Output contact 1
F8.8E.ai
Figure 8.6 Contact Setup Display
Figure 8.7 Output Contact 1 Display
Warm up:
ON
Range change:
OFF
Calibration:
OFF
Maintenance: ON
Blow back:
OFF
Temp.input high:
OFF
Cal.gas press.low:
OFF
Process up set:
OFF
Enter
Contact1
Others
F8.9E.ai
Figure 8.8
“Contact1 Others” Display
Содержание EXAxt ZR22G
Страница 15: ...Blank Page...
Страница 51: ...Blank Page...
Страница 77: ...Blank Page...
Страница 137: ...Blank Page...
Страница 171: ...Blank Page...
Страница 195: ...Blank Page...
Страница 197: ......
Страница 199: ......
Страница 201: ......
Страница 203: ......
Страница 205: ......
Страница 207: ......
Страница 211: ...Blank Page...