12
IM 04L41B01-19E
Data Mapping
Data mapping for each model is shown in the table. The following symbols are used in
the table.
Symbol
Explanation
CH1, CH2
Data of the measurement channel 1 or measurement channel 2.
CH101, CH112
Data of the computation channel 101 or computation channel 112.
C01, C24
Communication input data.
INT16
16-bit signed integer.
INT32_B
32-bit signed integer, BigEndian*.
* BigEndian: Assuming that a value of 01020304H is located as 01 02 03 04 in the buffer.
Note
• To acquire a physical value of the measurement channel data or computation channel data,
it is necessary to obtain the
decimal place and
unit information in advance.
• The channel data or communication input data that cannot be allocated in the I/O buffer is
not supported..
DX1002
Mapping of the input buffer
Offset
Description
Data type
0 – 1
CH1
INT16
2 – 3
CH2
4 – 7
CH101
INT32_B
8 – 11
CH102
12 – 15
CH103
16 – 19
CH104
20 – 23
CH105
24 – 27
CH106
28 – 31
CH107
32 – 35
CH108
36 – 39
CH109
40 – 43
CH110
44 – 47
CH111
48 – 51
CH112
52 – 127
Always 0.
-