4 . INSTALLATION
4.5 Rotating Transmitter Section
The transmitter section can be rotated approximately
360
°
(180
°
to either direction or 360
°
to one direction
from the original position at shipment, depending on
the configuration of the instrument.) It can be fixed at
any angle within above range.
1) Remove the two setscrews that fasten the transmitter
section and capsule assembly, using the Allen
wrench.
2) Rotate the transmitter section slowly and stop it at
designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than
the above limit.
F0407.EPS
Vertical impulse piping type
Horizontal impulse piping type
Pressure-detector section
Transmitter section
Rotate 0 to
±
180
°
segments
Rotate 0 to
±
180
°
segments
Transmitter section
Pressure-detector section
Conduit connection
Conduit connection
Zero-adjustment screw
Stopper
Figure 4.7
Rotating Transmitter Section (Left Side High
Pressure Type)
4.6 Changing the Direction of
Integral Indicator
IMPORTANT
Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
before disassembling and reassmbling an
indicator.
An integral indicator can be installed in the following
three directions. Follow the instructions in section 8.4
for removing and attaching the integral indicator.
F0408.EPS
Figure 4.8
Integral Indicator Direction