IM 01C22T01-01E

1-1

1.  ZERO POINT ADJUSTMENT

1.

ZERO POINT ADJUSTMENT

After operating preparation is completed, adjust the
zero point. The zero point adjustment can be made
using either of the following two methods.

For output signal checking, display the parameter 

%

rnge

 in the HART Communicator.

HART Communication
display

EJA:
Process variable
 1 Pres

0.012nnH2O

 2 % range

 0.00%

 3 A01 Out

4.002mA

 4 Snsr temp

38.1C

 5 Static pres

HELP

DIAG

HOME

ESC

F0101.EPS

Zero-adjustment
screw

Using the Transmitter Zero-adjustment
Screw

Before using the zero-adjustment screw outside the
transmitter case, confirm the following.

Ext SW mode

 must be 

ENABLE

. See Subsection

2.3.3 (17) for the setting procedure.

• Use a slotted screwdriver to turn the zero-adjustment

screw. Turn the screw clockwise to increase the
output or counterclockwise to decrease the output,
the zero point adjustment can be adjusted with a
resolution of 0.01% of the setting range.

The degree of zero adjustments varies with the

screw turning speed. Therefore, turn the screw
slowly for fine adjustment and quickly for coarse
adjustment.

CAUTION

Do not turn off the power to the transmitter
immediately after a zero adjustment. Powering
off within 30 seconds after a zero adjustment will
return the adjustment back to the previous
settings.

Using the HART Communicator

Zero point can be adjusted by simple key operation of
the HART Communicator.

Select parameter 

Zero Trim

, and press the 

OK (F4)

key twice. The zero point will be adjusted automati-
cally to the output signal 0% (4 mA DC). Confirm that
the setting value displayed for the parameter 

% rnge

is 

0.0%

 before pressing the 

OK (F4)

 key. See Subsec-

tion for HART Communicator operating procedures.

1.1 Zero Point Adjustment

The DPharp supports several adjustment methods.

Select the method best suited for conditions matching
the state of the site.

Note that output signal can be checked by HART
Communicator.

Adjustment Method

Description

Zero adjustment 
using the HART 
Communicator

Set the present 
input to 0%.
P.1-2 ‘Zero trim’

Zero adjustment 
using the 
external zero-
adjustment 
screw

Adjust zero point using the zero-
adjustment screw on the transmitter.
This permits zero adjustment without 
using the HART Communicator.
Accurately adjust the output current to 
4mA DC or other target output value 
using an ammeter that accurately reads 
output currents.

Adjust for 0% output 
at input level of 0%.

Adjust output to 
the reference 
value obtained 
using other 
means.
P.1-2 ‘Lower 
sensor trim’

If the input level 
cannot easily be 
made 0% (because of 
tank level, etc.), 
adjust output to the 
reference value 
obtained using other 
means, such as a 
glass gauge.

T0101.EPS

Содержание Dpharp vigilantplant EJA Series

Страница 1: ...User s Manual Yokogawa Electric Corporation Model EJA Series HART Protocol IM 01C22T01 01E IM 01C22T01 01E 7th Edition...

Страница 2: ...ion 2 5 2 3 2 Menu Tree 2 6 2 3 3 Setting Parameters 2 7 1 Tag No 2 7 2 Unit 2 7 3 Range Change 2 7 4 Output Mode Linear Sq root 2 8 5 Damping Time Constants 2 9 6 Output Signal Low Cut Mode Setup 2 9...

Страница 3: ...110 EJA120 IM 01C22B01 01E EJA210 EJA220 IM 01C22C01 01E EJA310 EJA430 IM 01C22D01 01E EJA118W EJA118N EJA118Y IM 01C22H01 01E EJA438W EJA438N IM 01C22J01 01E EJA115 IM 01C22K01 01E T01 EPS Manual No...

Страница 4: ...adjustment will return the adjustment back to the previous settings Using the HART Communicator Zero point can be adjusted by simple key operation of the HART Communicator Select parameter Zero Trim a...

Страница 5: ...smitter output 1383 mmH2O DPharp F0103 EPS 1 1 Device setup 2 Diag Service 3 Calibration 3 Sensor trim 2 Lower Sensor Trim EJA Apply low pressure ABORT OK F0104 EPS Check the tank level at present and...

Страница 6: ...e setting push button The integral indicator then displays LSET 3 Apply a pressure of 0 kPa atmospheric pressure to the high pressure side of the transmitter Note 1 4 Turn the external zero adjustment...

Страница 7: ...ging LRV automatically changes URV to the following value URV previous URV new LRV previous LRV 3 If the range setting push button and external zero adjustment screw are not touched during a range cha...

Страница 8: ...from any terminal strip as well DPharp HART communicator Relaying terminals Distributor Control room Terminal board F0201 EPS HART communicator Figure 2 1 1 Interconnection Diagram 2 1 2 Communicatio...

Страница 9: ...s the position where a number or character is to be entered Pressing calls up the display corresponding to the item pointed with the highlighting cursor Pressing returns to the previous display See 2...

Страница 10: ...re establish communication EXIT leave the current menu YES answer to yes no question ALL include current Hot Key item on Hot Key Menu for all devices F2 ON OFF activates or deactivates a binary variab...

Страница 11: ...is held in memory unless power is turned off every data can be sent to the transmitter at once Operation Entering data on the Tag setting display 1 Device setup 3 Basic setup 1 Tag F0206 EPS EJA YOKO...

Страница 12: ...f self test calibration of transmitter Display the status of 4 to 20 mA DC output when a failure Display set the external volume protect permit for LRV URV setting Setting a new password Set the curre...

Страница 13: ...m Point 1 Sensor Temperature 2 Sensor Temperature Unit 1 Static Pressure 2 Static Pressure Unit 1 PROCESS VARIABLES 2 RERANGE 3 Unit 4 Transfer Function 5 Damp 6 Low Cut 7 Cut Mode 8 Bi dir Mode 9 H2O...

Страница 14: ...R 3 Select the desired engineering unit and press ENTER F4 HELP 3 ENTER Example To change the unit from mmH2O to inH2O F02111 EPS EJA keypad input 1 LRV 0 00 mmH2O 2 URV 3000 00 mmH2O 3 Unit inH2O 4 L...

Страница 15: ...ABORT OK 3 Apply the pressure of 500mmH2O After obtaining a stable pressure press OK F4 ENTER OK OK 1 Device setup 3 Basic setup 3 Re range 2 Apply values Example To change the range from 0 to 2500 m...

Страница 16: ...circuit The damping constant of the capsule assembly shall be added to obtain the overall damping constant of the transmitter Table 2 0 2 Sec 0 5 Sec 1 0 Sec 2 0 Sec 4 0 Sec 8 0 Sec 16 0 Sec 32 0 Sec...

Страница 17: ...display Low Cut 4 mA 100 display Output mode SQUARE ROOT LRV HRV 8 Integral Indicator Display Mode F0220 EPS ENTER EJA Display fnctn Linear Linear Square Root HELP SEND ESC ENTER Select Square Root a...

Страница 18: ...ing units to be displayed on the HART communicator When the instrument is shipped this is set as specified in the order Follow the procedure below to change this setting Since these units are not disp...

Страница 19: ...nit from mmH2O to kPa inH2O inHg ftH2O mmH2O mmHg psi bar mbar g cm2 kg cm2 Pa kPa torr atm 12 Test Output This feature can be used to output a fixed current from 3 2 mA 5 to 21 6 mA 110 for loop chec...

Страница 20: ...or zero shifts caused by static pressure See section 1 1 1 1 F02281 EPS Select the Lower Sensor trim EJA Sensor trim 1 Zero trim 2 Pres 3 Lower sensor trim 4 Upper sensor trim 5 Sensor trim points HE...

Страница 21: ...000 HELP ESC 5 Enter the read value 4 115 of the ammeter and press ENTER F4 The output of the transmitter changes DEL ENTER ENTER 4 1 1 5 Example 1 For the adjustment using an ammeter 1 A is measurabl...

Страница 22: ...Connect reference meter DEL SET ABORT OK 7 Connect the voltmeter and press OK F4 EJA Setting fld dev output to 4mA HELP DEL ABORT OK 8 Press OK F4 The output signal of 0 is output OK OK ENTER F0233 EP...

Страница 23: ...lay and set to OFF 16 Multidrop Mode Multidropping transmitters refers to the connection of several transmitters to a single communications transmission line Up to 15 transmitters can be con nected wh...

Страница 24: ...zero adjustment screw on the transmitter This is set to ENABLE when the instrument is shipped F0237 EPS ENTER EJA Ext SW mode Enable Enable Inhibit HELP SEND ESC ENTER Select Inhibit and press ENTER...

Страница 25: ...s Write Protect status for 10 minutes While Write Protect status is released enter a new password in the New Password field It will not be possible to set a new password when 10 minutes have elapsed 2...

Страница 26: ...select F0241 EPS ENTER EJA H2O Unit select 4C 4C 20C 68F HELP SEND ESC ENTER Select 20C 68F and press ENTER F4 Press SEND F2 to send data SEND 1 Device setup 4 Detailed setup 2 Signal condition 9 H2O...

Страница 27: ...o low Operation is set in the Write Protect mode Value is set to a nearest possible value LRV set point is too high LRV set point is too low URV set point is too high URV set point is too low Set span...

Страница 28: ...modify as needed Check URV and modify as needed Check SPAN and change as needed Readjust zero point Replace capsule Replace amplifier Check input Integral Indicator Display Description Cause Counterme...

Страница 29: ...Pressure variable output variable 4 to 20 mA output variable Sensor temperature Static pressure Output in Engr unit Test output setting Self test Status Status of analog output alarm Write Protect En...

Страница 30: ...emote seal Remote seal fill fluid Remote seal type Distributor Device type Device ID Final assembly number Universal revision Fld dev revision Software revision Model Style Lower range limit Upper ran...

Страница 31: ...nts and the associated page numbers may not coincide with the one in old edition Add Hardware Write Protect and Burnout Direction with optional code F1 REVISION RECORD EPS 4th July 2000 ii 2 6 2 18 3...

Отзывы: