3-1
IM 01C25B01-01E
3. Component Names
HIGH
LOW
Slide switch
Burnout direction switch
Write protection switch
Burnout Direction
Switch Position
BO H
L
WR E
D
H
L
H
L
Burnout direction switch (BO)
Burnout Direction
F0301.ai
Write Protection
Switch Position
H
L
E
D
H
L
E
D
Write Protection
Hardware write protection switch (WR)
YES
(Write disabled)
NO
(Write enabled)
Vertical impulse piping type
Pressure-detector section
Cover flange
Terminal box cover
Horizontal impulse piping type
External indicator
conduit connection
(Note 1)
Vent plug
Drain plug
Transmitter section
Integral
indicator
(Note 1)
Mounting screw
Push button
(Note 1)
(See section 7.6)
Amplifier Cover
CPU assembly
Zero-
adjustment
screw
Conduit
connection
Process
connector (Note 1)
Process
connection
(Note 2)
Note 1: See General Specifications sheet of each product for details. A process connector will not be applied for lower side of
EJ
310
, EJ
430
, and EJ
440
.
Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the figure above to set the burn-out direction
and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specified in the order),
and the hardware write protection switch is set to E side. The setting of the switches can be confirmed via communication. An
external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating
the hardware write protect function. See each communication manual.
Figure 3.1
Component Names
Table 3.1
Display Symbol
F0302.ai
Display Symbol
Meaning of Display Symbol
Display mode is ‘square root’. (Display is not lit when ‘linear’ mode.)
The output signal being zero-adjusted is increasing.
Besides, this symbol lights when local parameter setting is in progress.
The output signal being zero-adjusted is decreasing.
Besides, this symbol lights when local parameter setting is in progress.
Write protect function is enabled.