5-14
IM CW500-01EN
When the target value entry window is displayed, the following operations
become valid. You can specify an active power or apparent power for
the demand target value. To switch between active power and apparent
power, press F1 (VA/W) to change to the appropriate power unit.
*
To
change the unit,
*
use the left and right arrow keys to move to the unit, and
use the up and down arrow keys to change it. Press F2 and F3 to move
the decimal point.
* Apparent power:mVA, _VA, kVA, MVA, GVA, TVA
Active power:mW, _W, kW, MW, GW, TW
Inspection cycle
Select the cycle (time) during which a buzzer is sounded when the
estimated value exceeds the target value during demand measurement.
You cannot set the inspection cycle longer than the measurement
cycle. The inspection cycles that can be selected depending on the
measurement cycle are shown below.
Measurement cycle setting
Selectable inspection cycles
10 min or 15 min
1 min, 2 min, 5 min
30 min
1 min, 2 min, 5 min, 10 min,
*
15 min
* Default value
<Procedure>
Use the up and down arrow keys to move to Inspection.
→
Press ENTER
to show a value entry window.*
→
Use the arrow keys to select the time.
→
Press ENTER to confirm or ESC to cancel.
* The input range is shown in a pop-up.
5.3 Measurement Setup