1. System Installation Requirements
1-10
TI 33Q01J10-01E
Installation Environment Specifications
The following table lists environmental requirements for the installation of the CS 3000 system:
For environmental requirements for devices including PC and UPS, refer to their environmental
specifications.
SEE
ALSO
For details, refer to the hardware general specifications (GS) for each equipment.
Table Equipment Installation Specifications (1/2)
Item
Specifications
(LPCKIT)
Specifications
(YPCKIT, YAX101 and YAX801)
Temperature
Normal operation
5 to 40 °C
YPCKIT: 5 to 35 °C
YAX101, YAX801: 5 to 40 °C
Transportation/storage –20 to 60 °C
–20 to 60 °C
Humidity
Normal operation
20 to 80 %RH
20 to 80 %RH
Transportation/storage 20 to 80 %RH
20 to 80 %RH
Temperature
fluctuation
Normal operation
Within ±10 °C/h
Within ±10 °C/h
Transportation/storage Within ±20 °C/h
Within ±20 °C/h
Power
source
Voltage range
100-120 V AC ±10 %
220-240 V AC ±10 %
100-120 V AC ±10 %
220-240 V AC ±10 %
Frequency
50/60 ±3 Hz
50/60 ±3 Hz
Distortion factor
10 % or less
10 % or less
Peak value
125 V or larger (for 100-120 V)
275 V or larger (for 220-240 V)
125 V or larger (for 100-120 V)
275 V or larger (for 220-240 V)
Momentary failure
20 ms or less
20 ms or less
Withstanding voltage
1500 V AC/min.
1500 V AC/min.
Insulation resistance
20 M ohms/500 V DC
–
Grounding
100 ohms or less
100 ohms or less
Noise
Electric field
3 V/m or less (26 MHz to 1.0 GHz)
3 V/m or less (1.4 to 2.0 GHz)
1 V/m or less (2.0 to 2.7 GHz)
3 V/m or less (26 MHz to 1.0 GHz)
3 V/m or less (1.4 to 2.0 GHz)
1 V/m or less (2.0 to 2.7 GHz)
Magnetic field
30 A/m or less (AC)
400 A/m or less (DC)
30 A/m or less (AC)
400 A/m or less (DC)
Static electricity
4 kV or less (direct discharge)
8 kV or less (aerial discharge)
4 kV or less (direct discharge)
8 kV or less (aerial discharge)
Vibration
Vibration
Displacement amplitude:
0.25 mm or less (1 to 14 Hz)
Acceleration:
2.0 m/s
2
or less (14 to 100 Hz)
Displacement amplitude:
0.25 mm or less (1 to 14 Hz)
Acceleration: 2.0 m/s
2
or less
(14 to 100 Hz)
excl. LCD
Quake resistance
4.9 m/s
2
or less
4.9 m/s
2
or less excl. LCD
Vibration during
transportation
Horizontal: 2.9 m/s
2
or less
Vertical: 4.9 m/s
2
or less
Horizontal: 2.9 m/s
2
or less
Vertical: 4.9 m/s
2
or less
Impact
Transportation impact Horizontal: 49 m/s
2
or less
Vertical: 98 m/s
2
or less
Horizontal: 49 m/s
2
or less
Vertical: 98 m/s
2
or less
Dust
0.3 mg/m
3
or less
0.3 mg/m
3
or less
Corrosive gas
Class A, JEIDA-63
Class A, JEIDA-63
Note: The above specifications apply to a KIT only.
Sep. 30, 2008-00