<5. Functions>
69
IM 01E21A02-03EN
5.2.6 Totalization Direction Setting
The totalization direction can be specified when using the totalization function.
The setting can be configured with the following parameters.
Menu path
Display
Device setup ► Detailed setup ► Totalizer ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
70
Totalizer 1 ► Options Totalizer1 ► Total 1 Options
Specifies the totalization
direction of totalizer 1.
STB
79
Totalizer 2 ► Options Totalizer2 ► Total 2 Options
Specifies the totalization
direction of totalizer 2.
From the table below, select the totalization direction.
Selection
Description
Display
F
OUNDATION
Fieldbus
Balanced
Balanced
Totalizes the flow rate (difference) of the forward and reverse directions.
Absolute
Absolute
Totalizes the absolute value of the flow rate.
Only positive
OnlyPositive
Totalizes only the flow rate in the forward direction.
Only negative
OnlyNegative
Totalizes only the flow rate in the reverse direction.
Hold
Hold
Stops totalization processing (holding the current totalized value).
5.2.7 Totalized Value Reset/Preset Function
The reset/preset function can be specified for the totalized value. If the reset function is used,
the function resets the totalized value to “0”. If the preset function is used, it sets the preset value
specified in advance to the totalized value. The preset function is used when starting to count
totalization from the specified value.
The setting can be configured with the following parameters.
Use of the reset/preset function
Menu path
Display
Device setup ► Detailed setup ► Totalizer ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
72
Totalizer 1 ►
Reset/Preset
Totalizer1 ► Total 1 Preset
Uses the reset/preset
function of totalizer 1.
STB
81
Totalizer 2 ►
Reset/Preset
Totalizer2 ► Total 2 Preset
Uses the reset/preset
function of totalizer 2.