<5. Functions>
67
IM 01E21A02-03EN
Setting conversion factor for scaling
Menu path
Display
Device setup ► Detailed setup ► Totalizer ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
66
Totalizer 1 ►
Conv factor
Totalizer1 ► Total 1 Conv Factor Specifies the conversion
factor of totalizer 1.
STB
75
Totalizer 2 ►
Conv factor
Totalizer2 ► Total 2 Conv Factor Specifies the conversion
factor of totalizer 2.
Display of the totalized count value that is scaled with the conversion
factor
Menu path
Display
Device setup ► Process variables ► Totalizer ►(see below)
F
OUNDATION
Fieldbus
-
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
-
-
Totalizer 1 count
-
Displays the scaled totalized
value of totalizer 1.
-
-
Totalizer 2 count
-
Displays the scaled totalized
value of totalizer 2.
Example:
Set the unit of totalizer 2 to “m
3
” and the conversion factor to “2”.
-> If the totalized value of totalizer 2 is “10.123 m
3
”, the totalized value is scaled to “10.123÷2 = 5”.
5.2.3 Totalization Switch Function
When a target value (threshold) to totalize is specified, it can be used as a totalization switch
function. The totalization switch function can compare the specified target value with the totalized
value and output the result in status output.
The status output is active while the totalized value exceeds the specified target value.
For details about the output, active direction, and status output function setting for each terminal,
refer to Section 5.14. However, the status output function can be used only when disconnected
offline from the control loop.
The setting can be configured with the following parameters.
Menu path
Display
Device setup ► Detailed setup ► Totalizer ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► STB ► Device Configuration ► Configuration ► Totalizer ► (see
below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
STB
74
Totalizer 1 ► Set point Totalizer1 ► Total 1 Setpoint
Specifies the target value of
totalizer 1.
STB
83
Totalizer 2 ► Set point Totalizer2 ► Total 2 Setpoint
Specifies the target value of
totalizer 2.