<5. Functions>
164
IM 01E21A02-03EN
5.14 Pulse Output, Frequency Output, and Status
Output
NOTE
The pulse output, frequency output and status output should be used only at calibrating, and not
used when normally running.
5.14.1 Outputs of I/O2 Terminals
Use the I/O2 terminal only when calibrating. The I/ O2 terminal can be used as the pulse output,
frequency output, and status output.
The setting can be configured with the following parameters.
Menu path
Display
Device setup ► Detailed setup ► Pulse/Status out ► PO1/SO1 ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► MTB ► Device Configuration ► Maintenance ► Pulse/Status Out
► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
MTB
102
Output mode
Pulse 1 Output Mode
Specifies the output of the I/O2
terminal.
From the table below, select the output of I/O2 terminal.
Selection
Description
Display
F
OUNDATION
Fieldbus
No function
No function
Does not use the terminal.
Fixed pulse output
Fixed Pulse Output
Sets to the fixed pulse output.
Frequency output
Frequency Output
Sets to the frequency output (Duty 50%).
Status output
Status Output
Sets to the status output.
For details about the status output, refer to Subsection 5.14.6.
5.14.2 Alarm Output Function
The alarm output function can be used when using the frequency output or pulse output. This
function can be set the output operation to be performed when an alarm has activated.
The setting can be configured with the following parameter.
Menu path
Display
Device setup ► Detailed setup ► Pulse/Status out ► PO1/SO1 ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► MTB ► Device Configuration ► Maintenance ► Pulse/Status Out
► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
MTB
109
Alarm out
Pulse 1 Alarm Out
Specifies the alarm output
function for the frequency
output or pulse output.