5.10.2 Test Value Setting
It is necessary to set a test value for the terminal output value (pulse/status) and the process
value.
The setting can be configured with the following parameters.
However, the unit of the process value to test is the unit specified in Subsection 5.1.4. If the unit is
changed, the process value is also changed in conjunction with the changed unit.
Menu path
Display
Device setup ► Diag/Service ► Test ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► MTB ► Device Configuration ► Query Device ► MaintTB Original
Parameters(Part2) ► Page 4 ► Test ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
MTB
97
Velocity
Velocity Test Value
Sets the display item to the flow
velocity.
MTB
98
PO1
P1 Test Value
Specifies the frequency of
pulse output or frequency
output 1 for the I/O2 terminal.
MTB
99
SO1
SO1 Test Value
Specifies the status of status
output 1 for the I/O2 terminal.
5.10.3 Test 2 Mode
Test 2 Mode is the function to perform a test to the process value, analog output, totalized value
and pulse at once.
The test value can be set in the range between -10.0% and 110.0%.
Input test values (%) are tested with a scale value in response to the span of each process value.
Menu path
Display
Device setup ► Diag/Service ► Test ► (see below)
F
OUNDATION
Fieldbus
Device Configuration ► MTB ► Device Configuration ► Query Device ► MaintTB Original
Parameters(Part2) ► Page 4 ► Test ► (see below)
Block
Name
Relative
Index
Parameter
Description
Display
F
OUNDATION
Fieldbus
MTB
100
Test 2 mode
Test 2 Mode
Setting Test 2 mode
MTB
101
Test 2 value
Test 2 Output Value
Setting Test 2 mode value
From the table below, select the setting for Test 2 mode.
Selection
Display
F
OUNDATION
Fieldbus
Normal
Normal
Test
Test