<5. Functions>
133
IM 01E21A02-03EN
5.9.6
Verification (Device Health Diagnosis) Function
The verification function diagnoses the health of the product and displays the diagnosis result. It
takes about 15 minutes to complete the verification function, and the progress of the verification
function can be checked via the bar graph and the remaining time shown on the display.
10:00
Verification execution
Excitation circuit...
01 : 00
SET
SFT
INC
This function can inspect each condition of the magnetic circuit, excitation circuit, and calculation
circuit, and executes the device health diagnosis of the product based on their internal alarm
record along with their wiring misconnection. This function evaluates the diagnosis result based
on the conditions of the product and shows “Passed” if no problem is found or “Failed” if a
problem is found on the display.
The following execution results are shown on the display.
• Examples of “Passed” results
VF check results
Passed
VF Operation time
00001D 10:01
Magnetic circuit result
Passed
Exciting circuit result
Passed
Calculation circuit result Passed
Device status result
Passed
Connection status result Passed
• Examples of “Failed” results
VF check results
Failed
VF Operation time
00001D 10:01
Magnetic circuit result
Passed
Exciting circuit result
Passed
Calculation circuit result
Failed
Device status result
Passed
Connection status result Passed
Contact Yokogawa service center if the “Failed” message is displayed for items from “Magnetic
circuit result” to “Device status result”.
If “Failed” is displayed for “Connection status result”, check for wiring misconnection between the
sensor and transmitter (refer to Subsection 5.9.5 for detail) and damage on the cables.
The verification function can be used in two ways depending on the state of the fluid; one state
where a fluid is flowing and another state where no fluid is flowing.
The two diagnosis results (current and previous) are stored in the device memory, and they can
be checked later.
If the verification function is used, the following results can be displayed.
Total judgment result
Calculation circuit diagnosis result
Operation time of verification function
Device alarm diagnosis result
Magnetic circuit diagnosis result
Wiring connection diagnosis result
Excitation circuit diagnosis result
The setting can be configured with the following parameters.
Menu path
Display
Device setup ► Diag/Service ► Diagnosis ► (see below)
F
OUNDATION
Fieldbus
Diagnostic ► DTB ► Device Diagnostics ► Diagnostics/Alerts ► Diagnostics ► (see
below)