YH Basic

Operating instructions

YH BASIC Control Panel

Содержание YH Basic

Страница 1: ...EN YH Basic Operating instructions YH BASIC Control Panel ...

Страница 2: ... 3 3 Overview 4 4 Heating operation 5 5 Ventilation Operation 6 6 Error reporting 6 7 Set Temperature Control 7 7 1 Standart mode 7 7 2 Room thermostat mode 7 8 Resetting the Device 8 9 Information Screen 8 10 Cleaning 8 11 Error codes 9 11 Technical information 15 ...

Страница 3: ... no liability for defects damage and damages caused by non compliance with the installation instructions and user manual as well as the warnings provided within them This disclaimer applies especially to Improper use Repairs not carried out by a Yılkar service workshop Use of non genuine parts Conversion of the unit without permission from Yılkar 2 Safety Explosion hazard in environments with flam...

Страница 4: ...ter shutdown button 5 seconds 2 Ventilation On Off 2 4 3 3 Overview 4 6 5 3 Increase direction button 4 Decrement direction button 5 Ambient temperature sensor 6 Display screen Ventilation active Heating active Error alert Symbols ...

Страница 5: ...while in heating Follow the instructions 5 Increasing or decreasing the set temperature can be done with the arrow keys For the function of the set temperature see s 7 Heating stop If you press the button with the heating icon the heater will stop if heating is active The heating sign will disappear from the screen Attention If you press the fan button while in heating state the heating stops agai...

Страница 6: ... sign appears on the screen If you press the button with the ventilation icon again the ventilation mode is stopped Attention If you press the heating button while the ventilation is on the ventilation stops again The device starts heating 6 Error reporting If the device detects any error it will show an error code on the screen You can find information about the problem and how to fix it from the...

Страница 7: ...ermostat mode There is one temperature sensor on your control panel to detect the ambient temperature If you switch your device to room thermostat mode your heater will compare the temperature perceived by this sensor and bring the environment to the set temperature To activate the room thermostat mode consult your Yılkar authorized service center or follow the instructions specified in the instal...

Страница 8: ...creen The demonstration switches to the main menu after 3 seconds 9 Information Screen 10 Cleaning Please use only a soft lint free cloth for cleaning the control panel Moisture should not get into the body Do not use glass cleaners household cleaners sprays solvents alcohol containing or abrasive cleaners It is forbidden to include the control panel in domestic waste Please observe the national l...

Страница 9: ... the glow plug If no problems are observed in the cable sockets and current test replace the YHC Reset the device from the button or disconnect the system from the power supply and connect again E 02 Glow Plug High Current Cause The cable may be cut or the socket may be disconnected The fuel pump may have failed Device Response If the system detects an error while in the stop mode the system will ...

Страница 10: ...nction Troubleshooting Check the fan motor cable and sockets Unplug the fan motor cable from the YHC and perform a resistance test If the resistance test is smooth Replace the YHC Reset the device from the button or disconnect the system from the power supply and connect again E 05 Blower Motor Open Circuit Cause Cable may be cut or short circuited If any part enters the suction impeller side whil...

Страница 11: ...t or the socket may be disconnected The overheating sensor may have failed Device Response When the device sees the error it wants to switch to stop mode Troubleshooting Check the internal temperature sensor cable and sockets Remove the internal temperature sensor and check by applying resistance test If the ohmic resistance is 1200 Ω replace the overheating sensor 20 C If the resistance test is O...

Страница 12: ...vice from the button If the fault code E09 Overheating Sensor Open Circuit is displayed the overheating sensor is faulty Replace the overheating sensor Or remove the overheating sensor and check it by performing a resistance test There is a short circuit if the ohmic resistance is too low Replace the overheating sensor If the resistance test is OK replace the YHC Reset the device from the button o...

Страница 13: ...e same situation 2 times in a row it will give the error Troubleshooting Make sure the exhaust outlet and combustion air intake hoses are not blocked or improperly installed Make sure there is fuel in the fuel tank Make sure the fuel hose is not blocked Make sure glow plug is working Try to start the device after refueling the fuel tank if the device does not work in 2 attempts it will give the sa...

Страница 14: ...e device may see fan motor high current failure Device Response When the device detects this error it will switch to stop mode if it is working Troubleshooting Make sure that no external elements get inside the device Ensure that the distance between the outside air impeller and the holder T plastic is within the standards Make sure that the YHC is in the correct position Be sure to reset the devi...

Страница 15: ...emperature sensor on the control unit Device Response If the device is working when it detects this error it will switch to stop mode by cooling Troubleshooting Replace the control unit After replacement reset the device from the button or disconnect the system from the power supply and connect again E 20 Control Unit Temperature Sensor Failure Opsiyonel 11 Technical information The Control Unit i...

Страница 16: ...o make changes is reserved Printed in Turkey Yılkar Airconditioned 2020 Vehicle Heating Cooling and Ventilation Systems Phone 90 224 215 53 28 pbx Fax 90 224 215 99 24 Address Küçükbalıklı Mah 580 Sok No 6 Osmangazi BURSA TURKEY www yilkarklima com ...