Setting 7: Binary
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 4095/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
Note:
BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
n
F3-03: Digital Input Option DI-A3 Data Length Selection
Determines the number of bits for the option card input that sets the frequency reference.
No.
Parameter Name
Setting Range
Default
F3-03
Digital Input Option DI-A3 Data Length Selection
0 to 2
2
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
u
F4: Analog Monitor Card Settings
These parameters set the drive for operation with the analog output option card AO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F4-01, F4-03: Terminal V1, V2 Monitor Selection
Selects the data to output from analog terminal V1. Enter the final three digits of U
o
-
oo
to determine which monitor data
is output from the option card. Some monitors are only available in certain control modes.
No.
Parameter Name
Setting Range
Default
F4-01
Terminal V1 Monitor Selection
000 to 999
102
F4-03
Terminal V2 Monitor Selection
000 to 999
103
Note:
Set “000” or “031” when using the terminal in through mode. This setting can adjust the V1 and V2 terminal output from PLC via
MEMOBUS/Modbus communications or a communications option.
n
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set as
a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to
10 V.
No.
Parameter Name
Setting Range
Default
F4-02
Terminal V1 Monitor Gain
-999.9 to 999.9%
100.0%
F4-04
Terminal V2 Monitor Gain
-999.9 to 999.9%
50.0%
F4-05
Terminal V1 Monitor Bias
-999.9 to 999.9%
0.0%
F4-06
Terminal V2 Monitor Bias
-999.9 to 999.9%
0.0%
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Terminal V1
1.
View the value set to F4-02 (Terminal V1 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in F4-01 will be output from terminal V1.
2.
Adjust F4-02 viewing the monitor connected to the terminal V1.
3.
View the value set to F4-05 on the digital operator, terminal V1 will output a voltage equal to 0% of the parameter
being set in F4-01.
4.
Adjust F4-05 viewing the output signal on the terminal V1.
1.6 F: Option Settings
68
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual